Technical information

Available pressure for the YLCA/YLHA 40 ÷ 150 hydraulic circuit with pack (no
filter fitted)
YLCA-YLHA TP model Flow l/h kPa
40
4750 261
5500 218
6250 166
7000 105
7500 60
8000 13
50
6500
149
7000 142
7500 135
8000 127
8500 119
9000 110
9500 100
10000 90
10500 79
11000 68
11500 56
12000 44
60
7500
233
8000 222
8500 210
9000 198
9500 185
10000 172
10500 156
11000 140
11500 122
12000 105
12500 86
13000 67
13500 47
80
9500
169
10000 164
10500 159
11000 154
11500 148
12000 143
12500 137
13000 131
13500 124
14000 118
14500 111
15000 103
15500 96
16000 87
16500 79
17000 71
17500 62
18000 53
18500 43
19000 33
YLCA-YLHA TP model Flow l/h kPa
100
12000
245
13000 236
14000 226
15000 215
16000 201
17000 187
18000 171
19000 153
20000 131
21000 110
22000 87
23000 57
24000 32
120
15000
310
16000 295
17000 279
18000 261
19000 241
20000 217
21000 187
22000 157
23000 123
24000 90
25000 55
150
18000
249
19000 243
20000 237
21000 230
22000 223
23000 215
24000 207
25000 199
26000 192
27000 183
28000 175
29000 165
30000 155
31000 145
32000 132
33000 120
34000 109
35000 95
36000 84
37000 70
38000 57
Data with water at 10°C.
If using glycol, apply the correction factors indicated in section (Ethylene glycol pressure drop correcting
factor and propylene glycol pressure drop correcting factors).
Technical Information