Technical information
Parameters relating to fans
Parameters relating to fans
Display Description Level VS Unit Max. Min. Value
F01
Fan outlet:
0= Absent (function not available
1= Present
F 10 (R/W) 1 0 1
F02
Operating mode:
0=Always ON (function not available)
1= parallel to the compressor (function not
available)
2=ON/OFF operation (function not availa‐
ble)
3= parallel to the compressor and speed
adjustment
U 48 (R/W) 3 0 3
F03 Minimum Triac voltage F 49 (R/W) step F04 0 35
F04 Maximum Triac voltage F 50 (R/W) step 100 F03 92
F05 Cool cycle minimum speed pressure F 24 (R/W) bar 80 -40 22,2
F06
Cool cycle maximum speed pressure dif‐
ferential
F 26 (R/W) bar 50 0 3,7
F07
Cool cycle fan stoppage pressure differen‐
tial
F 28 (R/W) bar 50 0 6,5
F08 Heat cycle minimum speed pressure F 30 (R/W) bar 80 -40 8,7
F09
Heat cycle maximum speed pressure dif‐
ferential
F 32 (R/W) bar 50 0 0,9
F10
Heat cycle fan stoppage pressure differen‐
tial
F 34 (R/W) bar F08 0 1,9
F11 Fan start-up time F 51 (R/W) Seconds 120 0 10
F12 Triac impulse duration F 52 (R/W) Seconds 10 0 2
F13
Fan management in defrost mode:
0= fan disabled
1= fan enabled in cool cycle mode (function
not available).
2= fan disabled until the defrost end tem‐
perature is reached and with top-speed
start-up during d16
F 53 (R/W) 2 0 2
F14
Fan operating when starting with high am‐
bient temperature
U 91 (R/W) Seconds 999 0 30
A Fan speed
B Condensing temperature
C Evaporating temperature
1 Technical Information
1.13 Operating instructions
60