Technical information

Parameters relating to sensors
Parameters relating to sensors
Display Description Level VS Unit Max. Min. Value
/01
NTC B1 sensor (water inlet):
0= Absent (function not available
1= Present
F 1 (R/W) - 1 0 1
/02
NTC B2 sensor (water outlet):
0=Always ON (function not available)
1= Present
F 2 (R/W) - 1 0 1
/03
NTC B3 sensor:
1= Condensation sensor
2= Outdoor sensor
F 14 (R/W) - 1 0 2
/04
B4 sensor:
0= Absent
1= ON/OFF
2= Outdoor NTC sensor
3= Ratiometric 5 Vdc
F 15 (R/W) - 3 0 3
/09 Minimum input voltage F 18 (R/W) 0.01 Vdc /10 0 50
/10 Maximum input voltage F 19 (R/W) 0.01 Vdc 500 /09 450
/11 Minimum pressure F 1 (R/W) bar /12 0 0
/12 Maximum pressure F 2 (R/W) bar 99,9 /11 45
/13 B1 sensor calibration F 3 (R/W) °C 12 -12 0
/14 B2 sensor calibration F 4 (R/W) °C 12 -12 0
/15 B3 sensor calibration F 5 (R/W) °C 12 -12 0
/16 B4 sensor calibration F 6 (R/W) bar 12 -12 0
/21 Digital filter U 20 (R/W) - 15 1 4
/22 Input limitation U 21 (R/W) - 15 1 8
/23
Measuring unit
0=C
1=1F
U 5 (R/W) - 1 0 0
b00 Sensor viewed on display U 24 (R/W) - 7 0 0
b01 Value read by sensor B1 D 70 (R) °C - - -
b02 Value read by sensor B2 D 71 (R) °C - - -
b03 Value read by sensor B3 D 72 (R) °C - - -
b04 Value read by sensor B4 D 73 (R) °C/bar - - -
Parameters relating to the compressor
Parameters relating to the compressor
Display Description Level VS Unit Max. Min. Value
c01 Minimum operating time U 25 (R/W) Seconds 999 0 120
c02 Minimum stoppage time U 26 (R/W) Seconds 999 0 60
c03 Time between start-ups of one compressor U 27 (R/W) Seconds 999 0 300
c06 Start-up timing U 30 (R/W) Seconds 999 0 10
c07 Compressor start-up delay with regard to the pump U 31 (R/W) Seconds 150 0 20
c08 Pump stoppage delay with regard to the compressor U 32 (R/W) Minutes 150 0 1
c10 Operating hour counter for compressor D 90 (R) Hours 800 0 -
c14 Operating hour counter for compressor maintenance U 34 (R/W) Hours 100 0 0
c15 Operating hour counter for pump D 94 (R/W) Hours 800 0 -
c17 Minimum time between pump start-ups U 35 (R/W) Minutes 150 0 5
c18 Minimum operating time for pump U 36 (R/W) Minutes 15 0 1
Technical Information 1
Operating instructions 1.13
73