No. of pumps 1
Available static pressure at rated flow
(without filter) (2)
kPa 147 118 160 137 195 231 205
Available static pressure at rated flow (with
filter) (3)
kPa 137 117 158 134 192 228 200
Pump consumption W 1 035 990 1 515 1 580 2 380 3 180 3 400
Pump amperage A 1.9 1.80 2.9 3.2 4.4 5.5 6.1
Unit water content l 131 188 194 285 193 195 214
Expansion vessel volume l 12 18 25 35
Tank capacity l 115 170 260 152
Relief valve setting Bar 6
Max. unit power supply consumption kW 17.38 23.9 26.3 34.2 52.4 56.2 74.5
Max. unit current amperage A 36.2 45.1 49.2 69.8 95.4 108 120
Start-up amperage (compressor) A 174 118 118 174 118 118 174
Weight (1) kg 397 593 624 805 1 250 1 316 1 703
Start-up amperage (compressor) A 174 118 118 174 118 118 174
Pressure drop, cooling mode kPa 70 37 51 56 53 29.5 25.5
Unit water content 4 6 6 7 12 12 14
Max. unit power supply consumption kW 16.3 23 24.8 32.6 50 53 71.1
Max. amperage A 34.3 43.3 46.3 66.6 91 103 114
Weight (1) kg 337 537 568 735 1 154 1 220 1 615
Units without pack
(1) Weight for unit empty. (2) Available static pressure, Eurovent certified. (3) Pressure with clean filter.
Units with hydro kit (version P)