Data with water at 10°C.
In the case of using glycol, apply the correcting factors indicated in Fig. 5 and 6 of the Selection Guide section.
Table 6. Available pressure for hydraulic circuit YLCA/YLHA 40 ÷ 150 with pack (without filter
installed)
Model Flow l/h kPa
YLCA/YLHA 40 TP
4 750 261
5 500 218
6 250 166
7 000 105
7 500 60
8 000 13
YLCA/YLHA 50 TP
6 500 149
7 000 142
7 500 135
8 000 127
8 500 119
9 000 110
9 500 100
10 000 90
10 500 79
11 000 68
11 500 56
12 000 44
YLCA/YLHA 60 TP
7 500 233
8 000 222
8 500 210
9 000 198
9 500 185
10 000 172
10 500 156
11 000 140
11 500 122
12 000 105
12 500 86
13 000 67
13 500 47
YLCA/YLHA 80 TP
9 500 169
10 000 164
10 500 159
11 000 154
11 500 148
12 000 143
12 500 137
13 000 131
13 500 124
14 000 118
14 500 111
15 000 103
15 500 96
16 000 87
16 500 79
17 000 71
17 500 62
18 000 53
18 500 43
19 000 33
YLCA/YLHA 100 TP
12 000 245
13 000 236
14 000 226
15 000 215
16 000 201
17 000 187
18 000 171
19 000 153
20 000 131
21 000 110
22 000 87
23 000 57
24 000 32
YLCA/YLHA 120 TP
15 000 310
16 000 295
17 000 279
18 000 261
19 000 241
20 000 217
21 000 187
22 000 157
23 000 123
24 000 90
25 000 55
YLCA/YLHA 150 TP
18 000 249
19 000 243
20 000 237
21 000 230
22 000 223
23 000 215
24 000 207
25 000 199
26 000 192
27 000 183
28 000 175
29 000 165
30 000 155
31 000 145
32 000 132
33 000 120
34 000 109
35 000 95
36 000 84
37 000 70
38 000 57