Technical information
68
Parameters related to the probes
Display Description Level VS Unit Max. Min. Value
c01
Minimum operating time U 25 (R/W) Sec. 999 0
120
c02
Minimum OFF time U 26 (R/W) Sec. 999 0
60
c03
Time between start-ups of the same compressor U 27 (R/W) Sec. 999 0
300
c06
Start-up timing U 30 (R/W) Sec. 999 0
10
c07
Compressor start-up delay with regard to the pump U 31 (R/W) Sec. 150 0
20
c08
Pump OFF delay with regard to the compressor U 32 (R/W) Min. 150 0
1
c10
Operating hour counter for compressor D 90 (R) Hours 800 0 -
c14
Operating hour counter for compressor maintenance U 34 (R/W) Hours 100 0
0
c15
Operating hour counter for pump D 94 (R/W) Hours 800 0 -
c17
Minimum time between pump start-ups U 35 (R/W) Min. 150 0
5
c18
Minimum operating time for pump U 36 (R/W) Min. 15 0
1
Parameters related to the probes
Display Description Level VS Unit Max. Min. Value
/01
NTC B1 probe (water intake); 0=absent (function not available).
1=present
F 1 (R/W) - 1 0
1
/02
NTC B2 probe (water outlet). 0=absent (function not available).
1=present
F 2 (R/W) - 1 0
1
/03
NTC B3 probe . 1=condensation probe. 2=outdoor probe. F 14 (R/W) - 1 0
2
/04
Probe type B4, 0=absent, 1=ON/OFF, 2=outdoor NTC probe, 3=ra-
tiometric 5Vdc.
F 15 (R/W) - 3 0
3
/09
Minimum input voltage F 18 (R/W) 0.01 Vdc /10 0
50
/10
Maximum input voltage F 19 (R/W) 0.01 Vdc 500 /09
450
/11
Minimum pressure F 1 (R/W) bar /12 0
0
/12
Maximum pressure F 2 (R/W) bar 99.9 /11
45
/13
Calibration probe B1 F 3 (R/W) °C 12 -12
0
/14
Calibration probe B2 F 4 (R/W) °C 12 -12
0
/15
Calibration probe B3 F 5 (R/W) °C 12 -12
0
/16
Calibration probe B4 F 6 (R/W) bar 12 -12
0
/21
Digital filter U 20 (R/W) - 15 1
4
/22
Input limitation U 21 (R/W) - 15 1
8
/23
Measuring unit 0 = C; 1 = 1F U 5 (R/W) - 1 0
0
b00
Probe viewed on display U 24 (R/W) - 7 0
0
b01
Value read by probe B1 D 70 (R) °C - -
-
b02
Value read by probe B2 D 71 (R) °C - -
-
b03
Value read by probe B3 D 72 (R) °C - -
-
b04
Value read by probe B4 D 73 (R) °C/bar - -
-