Technical information
71
Parameters related to the fans
Display Description Level VS Unit Max. Min. Value
F01
Fan outlet. 0=absent (function not available); 1=present F 10 (R/W) 1 0
1
F02
Operating mode:
0= always ON (function not available)
1= Parallel with compressor (function not available)
2= ON/OFF operation (function not available)
3= Parallel with compressor and speed adjustment.
U 48 (R/W) 3 0
3
F03
Minimum triac voltage F 49 (R/W) step F04 0
50
F04
Maximum triac voltage
F 50 (R/W) step 100 F03
85
F05
Cool cycle minimum speed pressure F 24 (R/W) bar 80 -40
22.2
F06
Cool cycle maximum speed pressure differential F 26 (R/W) bar 50 0
3.7
F07
Cool cycle fan OFF pressure differential F 28 (R/W) bar 50 0
6.5
F11
Fan start-up time F 51 (R/W) Sec. 120 0
10
F12
Triac impulse duration F 52 (R/W) Sec. 10 0
2
F14
Fan in operation when starting with high ambient temperature U 91 (R/W) Sec. 999 0
30