Technical information
8
Characteristics
YLCA 40
T and TP
YLCA 50
T and TP
YLCA 60
T and TP
YLCA 80
T and TP
YLCA 100
T and TP
YLCA 120
T and TP
YLCA 150
T and TP
Cooling capacity kW 39.6 52.1 60.5 77.6 98 119 151
Capacity control % 0 - 100 50 - 100 25 - 50 - 75 - 100
Power supply V/ph 400.3.50
Compressor consumption kW 12.46 2 x 8.5 2 x 9.20 2 x 12.4 4 x 7.8 4 x 9.4 4 x 12.5
Compressor amperage A 23.5 2 x 15.5 2 x 16.7 2 x 24.6 4 x 16 4 x 17.7 4 x 23.5
EER 3.0 2.9 3.1 2.9 2.9 2.9 2.8
No. of refrigerant circuits 1 2
No. of compressors 1 2 (1 TANDEM) 4 (2 TANDEM)
Compressor type SCROLL
Oil charge l 3.25 2 x 3.25 4 x 3.25
Oil type POLYOL ESTER OIL
Evaporating unit type PLATES
Nominal water flow l/h 6 820 8 960 10 400 13 350 16 860 20 470 25 970
No. of fans 2 3 4
Fan diameter mm 560 630 710
Fan consumption W 2 x 400 2 x 600 3 x 600 4 x 600 4 x 860
Fan amperage A 2 x 1.9 2 x 2.8 3 x 2.8 4 x 2.8 4 x 3.9
Total air flow m
3
/h 12 300 18 600 27 500 36 000 48 000
Refrigerant type R-410A
Refrigerant charge kg 11 13 16 25 2 x 14 2 x 16.2 2 x 21
Sound power (STD) / (LN) dB (A) 81/76 84/78 85/80 86/82 86/82 86/82 87/83
Sound pressure at 5 m (STD) / (LN) dB (A) 60/54 62/56 63/57 66/60 63/60 64/60 65/61
Sound pressure at 10 m (STD) / (LN) dB (A) 54/48 56/50 57/51 60/54 57/54 58/54 59/55
Dimensions
Length mm 1 500 2 104 2 944 3 416 3 770
Width mm 822 1 011 1 118 1 101
Height mm 1 573 1 600 1 600 2 190 2 263
Water connection, female 1
1
/4" 2" 2
1
/2"
Water filter 1
1
/2" 2" 2
1
/2"
No. of pumps 1
Available static pressure at nominal
flow (without filter) (2)
kPa 115 110 160 126 190 205 192
Available static pressure at nominal
flow (with filter) (3)
kPa 105 108 158 123 187 202 186
Pump consumption W 1 035 990 1 515 1 620 2 395 3 180 3 400
Pump amperage A 1.9 1.8 2.9 3.3 44 5.5 6.1
Unit water content l 131 188 194 285 193 195 214
Expansion vessel volume l 12 18 25 35
Tank capacity l 115 170 260 152
Relief valve setting Bar 6
Max. unit power supply consumption kW 18.23 24.6 26.3 35.2 52.4 56.2 70.7
Max. unit current amperage A 33 46.2 49.2 70.5 95.4 108 124
Start-up amperage (compressor) A 174 118 118 174 118 118 174
Weight (1) kg 380 580 611 785 1 220 1 286 1 503
Start-up amperage (compressor) A 174 118 118 174 118 118 174
Water circuit pressure drop kPa 75 40 51 61 54 32 27.5
Unit water content 4 6 6 7 12 12 14
Max. unit power supply consumption kW 17.2 23.6 24.8 33.6 50 53 67.3
Max. unit current amperage A 174 44.4 46.3 67.2 91 103 118
Weight (1) kg 340 524 555 715 1 124 1 190 1 415
Physical data, cool only units
Units with hydro kit (version P)
Units without pack
(1) Weight for unit empty. (2) Available static pressure, Eurovent certified. (3) Pressure with clean filter.