Technical information
95
DESCRIPTION RANGE UNIT VALUE
Min. operating time of a compressor -99.9/99.9 °C 3
Antifreeze alarm set point differential 99.9 °K 5
Antifreeze alarm set point lower limit -99.9/99.9 °C 3
Antifreeze alarm set point upper limit -99.9/99.9 °C 5
Antifreeze alarm reset
MANUAL
AUTOMATIC
-
MANUAL
Antifreeze alarm delay (if automatic reset has been selected) 0/540 min. 0
Antifreeze heater activation set point -99.9/99.9 °C 3
Antifreeze heater activation set point differential -99.9/99.9 °K 2
Backup heater set point (winter cycle) -99.9/99.9 °C 25
Backup heater set point differential (winter cycle) -99.9/99.9 °K 5
Backup heater activation delay 0/60 min. 15
Antifreeze system automatic activation with the unit OFF
DISABLED
HEATER AND
PUMP
HEATER AND
UNIT HEATER
- HEATER
DESCRIPTION RANGE UNIT VALUE
Min. operating time of a compressor 0/9999 Sec. 120
Min. off time of a compressor 0/9999 Sec. 60
Start-up time between different compressors 0/9999 Sec. 3
Start-up time of one single compressor 0/9999 Sec. 300
Start-up time between pump and compressor 0/999 Sec. 20
Off time between compressor and pump 0/999 Sec. 20
Pump 1 operating hours
Pump 2 operating hours
Compressor 1 operating hours
Compressor 2 operating hours
Compressor 4 operating hours
Compressor 4 operating hours
Operating hours for pump maintenance alarm 1000/999000 hours 2x1000
Operating hours for compressor 1/circuit 1 maintenance alarm 1000/999000 hours 2x1000
Operating hours for compressor 2/circuit 1 maintenance alarm 1000/999000 hours 2x1000
Operating hours for compressor 1/circuit 2 maintenance alarm 1000/999000 hours 2x1000
Operating hours for compressor 2/circuit 2 maintenance alarm 1000/999000 hours 2x1000
Tandem compressor rotation time min. 20
Enabling of compressors C1/C2/, C1/ C2 YES/NO YES
Manual operation forced by the compressors YES/NO NO
-A- Antifreeze
-C- Compressors configuration