Technical information

97
DESCRIPTION RANGE UNIT VALUE
Unit type 0 - 7 -
2 (COOLER)
3 (HEAT PUMP)
No. of compressors/circuits - 4 / 2
Compressor rotation
LIFO
FIFO
PERSONALIZED
TIME
- FIFO
No. of evaporators 1 - 2 - 1
Driver number (EVD400) 0-1-2-4 - 0
Cycle inversion valve logic NO/NC - NC
No. of pumps 1 - 2 -
1 (SINGLE PUMP)
2 (TWO-PUMP ACCES-
SORY)
Pump rotation START-UP TIME - TIME
Pump operation
ON WITH COMP. ON
ALWAYS OFF
ALWAYS ON
SAFETY ON/OFF
ALWAYS ON
No. of hours for pump rotation 0-9999 hours 12
ON/OFF digital input activation YES/NO - NO
WINTER/SUMMER digital input activation YES/NO - NO
ON/OFF activation with monitor YES/NO - NO
WINTER/SUMMER activation with monitor YES/NO - NO
SUMMER/WINTER operation inversion delay Sec. 10
Monitoring protocol
CAREL
GSM MODEM
RS232
LONWORKS
MODBUS
- CAREL
Selection of communication speed
1200; 2400; 4800;
9600; 19200
bauds 19200
Monitoring ID number 0-200 - 1
Selection of language at start-up YES/NO - YES
Restore values by default (Attention!) YES/NO - NO
-H- Unit configuration