Technical information
99
DESCRIPTION RANGE UNIT VALUE
Set point
in COOL °C 12
Set point
in HEAT °C 40
Temperature control adjustment range °K 3
COOL set point lower limit °C 6
COOL set point upper limit °C 20
HEAT set point lower limit °C 25
HEAT set point upper limit °C 45
Temp. setting type
INPUT/OUTPUT
- INPUT
Setting type with input probe
PROPORTIONAL / P + 1
PROPORTIONAL
Integration time in each adjustment P + 1 0/9999 s 600
Max. increase time of call (output adjustment) 0/9999 s 20
Min. increase time of call (output adjustment) 0/9999 s 20
Max. decrease time of call (output adjustment) 0/9999 s 10
Min. decrease time of call (output adjustment) 0/9999 s 10
Temp. differential in which increase and decrease times vary (output adjustment) -99.9/99.9 °C 2
Forced off in COOL cycle (output adjustment) -99.9/99.9 °C 5
Forced off in HEAT cycle (output adjustment -99.9/99.9 °C 47
DESCRIPTION RANGE UNIT VALUE
High pressure alarm set point (B3; B4 transducer) 0/99.9 bar 41
High pressure alarm differential (B3; B4 transducer) 0/99.9 bar 10
Summer low pressure alarm 0/99.9 bar 3
Winter low pressure alarm 0/99.9 bar 2
Defrost low pressure alarm 0/99.9 bar 1
Low pressure differential 0/99.9 bar 1
Low pressure alarm delay at cool cycle start-up 0-999 s 60
Low pressure alarm delay at heat and defrost cycle start-up 0-999 s 0
Water flow switch alarm delay at start-up 0-999 s 20
Water flow switch alarm delay in operation 0-999 s 5
Number of off cycles per automatic reset alarms 0 - 4 1
Max. period for automatic reset alarms 0 - 99 m 60
Selection of automatic reset alarm: compressor thermal
AUTOMATIC/MANUAL
AUTOMATIC
Selection of automatic reset alarm: fan thermal
AUTOMATIC/MANUAL
AUTOMATIC
Selection of automatic reset alarm: low pressure switch
AUTOMATIC/MANUAL
AUTOMATIC
Selection of automatic reset alarm: high pressure switch
AUTOMATIC/MANUAL
AUTOMATIC
-P- Alarms
-r- Control
When this submenu is activated, the dynamic set point tem-
perature appears (if this function is enabled). Press "Down"
to access the configuration menu.