Specifications

43
Parameters related to defrost
Display Description Level VS Unit Max Min Value
d01
Execution of defrost 0= no (function not available) 1= yes. U 7 (R/W) - 1 0
1
d02
Time or temperature defrost.
0= time (function not available).
1= temperature
U 8 (R/W) - 1 0
1
d03
Defrost start temperature/pressure U 19 (R/W)
°C
bar
d04
-40/
11
-3
6.2
d04
Defrost end temperature/pressure U 21 (R/W)
°C
bar
80/
12
d03
20
14.4
d05
Minimum time for defrost start U 37 (R/W) sec. 150 10
10
d06
Minimum defrost duration U 38 (R/W) sec. 150 0
0
d07
Maximum defrost duration U 39 (R/W) Min. 15 1
6
d08
Time between two defrost cycles U 40 (R/W) Min. 150 10
30
d11
Activation of heaters in defrost
0= no.
1= yes.
U 9 (R/W) - 0 1
1
d12
Compressor OFF before defrost F 43 (R/W) Min. 3 0
1
d13
Compressor OFF after defrost F 44 (R/W) Min. 3 0
1
d16
Time of forced vent after defrost (only if F13=2). F 47 (R/W) sec. 360 0
60











