YLCA/YLHA PLUS 5 to 27 R-410A Ref: N-27723 0309M Technical Information � � � � � � � � ER-0028/1991 ��������� ISO 9001 ��������������������� ���������� Johnson Controls Manufacturing España. S.L. is participating in the EUROVENT Certification Program. Products are as listed in the EUROVENT Directory of Certified Products. in the program AC1. AC2. AC3. LCP and FC. The LCP program covers air condensed water chillers and heat pumps of up to 600 kW.
Index Page General Information 5 - 5 5 5 6 6 Nomenclature General description Models available and capacities Features and advantages Dynamic set point and suppression of buffer tank Technical Specifications 6 - 7 8 9 - Accessories and options Physical data. cool only units Physical data.
General Information Nomenclature Air/water water chiller with axial fans Approximate cooling capacity in kW R-410A Version Voltage M (single-phase 230.1.50) T (three-phase 400.3.50) With hydro kit (pack) Edition applications that require cold or hot water. They are silent and compact units, equipped with axial fans, and can be installed directly outdoors. Buffer tanks are available as accessories for installations that require a larger water volume.
Features and advantages Features Advantages R-410A refrigerant Does not harm the ozone layer. Minimum dimensions Minimum footprint. Low height and weight Space for installing on terraces. Factory tested equipment Operating quality control. Accessibility Easy maintenance. Main switch Operator safety. Microprocessor for control and alarms Easy and safe operation. Manufactured to ISO 9001 High quality level. Variable speed fan Low noise level and condensation control.
Hydro kit These units include a pack assembled with the components of a hydro kit. This assembly is located within the unit frame and does not increase the footprint of same. It includes the following components: Centrifugal pump, expansion vessel charged with nitrogen at 1.5 bar, relief valve set to 6 bar, flow switch, air bleed valve and drain connection. Also includes a mesh filter for the water circuit. This filter is supplied loose for installation at the most convenient point.
Physical data, cool only units YLCA-5 YLCA-7 YLCA-9 YLCA-7 M and MC M and MC M and MC T and TC Characteristics Cooling capacity kW Power supply 5.38 V/ph Compressor consumption Compressor amperage 7.13 YLCA-9 T and TC YLCA-12 T and TC YLCA-15 T and TC YLCA-20 T and TC YLCA-27 T and TC 14.50 19.52 25.6 8.63 7.13 8.63 12.4 230.1.50 400.3.50 kW 1.73 2.41 3.40 2.41 3.16 3.80 5.38 6.57 8.73 A 7.8 11.7 17 3.9 5.7 6.36 8.9 13 16.7 2.87 2.76 2.41 2.76 2.59 2.97 2.
Physical data, heat pump units YLHA PLUS-5 MC YLHA PLUS-7 MC YLHA PLUS-9 MC YLHA PLUS-12 MC YLHA PLUS-9 TC YLHA PLUS-12 TC YLHA PLUS-15 TC YLHA PLUS-20 TC YLHA PLUS-27 TC kW 5.4 7.10 8.7 11.75 8.7 12 13.8 19.4 25.8 kW 6.3 7.16 9.52 12.25 9.52 12.4 16.1 20.9 27.5 Characteristics Cooling capacity Heating capacity Power supply V/ph/Hz 230.1.50 400.3.50 Comp. consumption in cooling kW 1.77 2.41 3.29 3.90 3.29 3.80 5.13 6.71 8.47 Comp. consumption in heating kW 1.
Operation, cooling and hydraulic diagram, heat pump unit YLHA PLUS 5 to 15 2 B A 1 P P E ON 9 4 P 8 7 C 13 6 14 WATER OUTLET 11 3 5 F 12 WATER INTAKE E 4 10 SAFETY/CONTROL DEVICES COMPONENTS 10 Liquid receiver A High pressure switch 1 Compressor 11 Drain connection B Low pressure switch 2 Air cooled condenser 12 Water filter (not inside the unit) C Pressure transducer port 3 Filter dryer 13 Relief valve E Condensing unit temp.
Operation, cooling and hydraulic diagram, heat pump unit YLHA PLUS 20 and 27 2 B A 8 P 1 P E ON 9 8 5 14 12 10 6 3 10 7 13 F WATER OUTLET 17 15 16 18 WATER INTAKE 4 G 5 11 SAFETY/CONTROL DEVICES A High pressure switch B Low pressure switch E Condensing unit temperature sensors (fan speed setting and display) F Water outlet temperature sensor (antifreeze, setting and display) G Water intake temperature sensor (setting and display) COMPONENTS 1 Tandem compressor 2 Air cooled condens
Operation, cooling and hydraulic diagram, cool only unit YLCA A B P P 1 2 8 10 9 D 11 14 F C 7 P 12 8 6 13 WATER INTAKE WATER OUTLET E 3 4 5 YLCA-20. 27 (TEV) YLCA-5 to 15 (RESTRICTOR) 5 SAFETY/CONTROL DEVICES A High pressure switch COMPONENTS 10 Automatic air bleed 1 Compressor B Low pressure switch 11 Expansion vessel 2 Air cooled condenser C Pressure transducer port (LAK YLCA 5 to 15) Pressure sensor. Pressure reading.
Table 1. Cooling capacities YLCA 5 to 27 Cap. kW Unit kW Cap. kW Unit kW Outdoor ambient temperature °C DB (80% RH) 30 32 35 40 Cap. Unit Cap. Unit Cap. Unit Cap. Unit kW kW kW kW kW kW kW kW 5 5.71 1.59 5.55 1.63 5.31 1.70 5.18 1.76 4.99 1.85 4.41 2.06 4.18 2.18 3.92 2.33 6 5.93 1.59 5.76 1.64 5.52 1.71 5.38 1.77 5.18 1.86 4.68 2.07 4.43 2.21 4.18 2.35 7 6.15 1.60 5.98 1.65 5.73 1.72 5.59 1.77 5.38 1.87 4.95 2.08 4.69 2.23 4.44 2.38 8 6.31 1.60 6.
Table 2. Cooling capacities YLCA 5 to 27 (35% ethylene glycol) Model YLCA 5 7 9 12 15 20 27 14 Water outlet temp. °C Outdoor ambient temperature °C DB (80% RH) 20 25 30 32 35 40 43 46 Cap. Unit Cap. Unit Cap. Unit Cap. Unit Cap. Unit Cap. Unit Cap. Unit Cap. Unit kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 3.60 1.12 3.44 1.22 3.28 1.32 3.20 1.37 3.08 1.44 2.83 1.57 2.68 1.65 2.53 1.74 -4 3.79 1.15 3.63 1.24 3.44 1.35 3.36 1.
Table 3. Cooling capacities YLHA PLUS 5 to 27 Model YLHA PLUS 5M 7M 9M 9T 12 M 12 T 15 T 20 T 27 T Water outlet temp. °C 5 6 7 8 10 12 15 5 6 7 8 10 12 15 5 6 7 8 10 12 15 5 6 7 8 10 12 15 5 6 7 8 10 12 15 5 6 7 8 10 12 15 5 6 7 8 10 12 15 5 6 7 8 10 12 15 5 6 7 8 10 12 15 20 Cap. kW 6.00 6.25 6.50 6.60 6.70 6.80 7.00 7.60 7.75 7.90 8.05 8.30 8.55 8.90 9.31 9.50 9.68 9.86 10.17 10.48 10.91 9.31 9.50 9.68 9.86 10.17 10.48 10.91 12.63 12.90 13.40 13.55 13.74 14.15 14.73 12.9 13.17 13.69 13.84 14.
Table 4. Cooling capacities YLHA PLUS 5 to 27 (35% ethylene glycol) Model YLHA PLUS 5M 7M 9M 9T 12 M 12 T 15 T 20 T 27 T 16 Water outlet temp. °C -5 -4 -2 0 2 4 -5 -4 -2 0 2 4 -5 -4 -2 0 2 4 -5 -4 -2 0 2 4 -5 -4 -2 0 2 4 -5 -4 -2 0 2 4 -5 -4 -2 0 2 4 -5 -4 -2 0 2 4 -5 -4 -2 0 2 4 Outdoor ambient temperature °C DB (80% RH) 20 25 Cap. Abs. power kW 3.62 3.81 4.16 4.51 5.00 5.35 4.76 5.01 5.47 5.93 6.57 7.03 5.83 6.13 6.70 7.26 8.05 8.61 5.83 6.13 6.70 7.26 8.05 8.61 7.87 8.28 9.05 9.81 10.
Table 5. Heating capacities YLHA PLUS 5 to 27 Model YLHA PLUS 5M 7M 9M 9T 12 M 12 T 15 T 20 T 27 T Outdoor ambient temperature °C DB (80% RH) Water -15 -10 -7 0 5 7 10 15 20 outlet temp. Cap. Abs. Cap. Abs. Cap. Abs. Cap. Abs. Cap. Abs. Cap. Abs. Cap. Abs. Cap. Abs. Cap. Abs. power power power power power power power power power °C kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW 30 1.60 1.40 1.69 1.41 2.48 1.42 4.30 1.43 5.32 1.43 6.46 1.44 6.74 1.45 7.58 1.45 7.85 1.
Table 6. Available pressure for hydraulic circuit Table 6. (Cont.) (without filter installed) Model Model YLCA/ YLHA PLUS 05 Flow l/h DISP. kPa 600 61 800 55 1 000 46 1 200 36 1 400 YLCA/ YLHA PLUS 07 YLCA/ YLHA PLUS 09 YLCA/ YLHA PLUS 12 18 YLCA/ YLHA PLUS 15 Flow l/h DISP.
Table 7. Pressure drops of filters 1" filter Flow l/h 600 800 1 000 1 200 1 400 1 600 1 800 2 000 2 200 2 400 2 600 kPa 0.7 1.4 2.6 4.3 6.4 8.9 11.8 15.1 18.8 22.8 27.1 1 1/4" filter Flow l/h kPa 1 500 2 000 2 500 3 000 3 500 4 000 4 500 5 000 5 500 6 000 0.9 1.5 2.6 3.9 5.6 7.7 10.1 12.8 15.7 18.8 Data with water at 10° C. In the case of using glycol, apply correcting factors indicated in table 8. Table 8.
Selection guide (YLCA and YLHA PLUS) Necessary information The following information is needed to select a YLCA water chiller: 1. Cooling capacity needed. 2. Design cold water input and output temperatures. 3. Design water flow, if any of the temperatures in above point 2 is unknown. 4. Design input temperature of air to the condensing unit. Normally, this will be the design ambient temperature of summer air, unless influenced by the situation or other factors. 5. Altitude above sea level. 6.
All values are within operating limits. - Available pressure in hydraulic circuit of a unit with hydro kit. - From Table 6 we infer that the YLHA PLUS 5, with a 748 l/h flow, has an available pressure of 56.5 kPa. - Pressure drop in filter. - From Table 7.1" filter, we infer that with a 748 l/h flow, said filter has a pressure drop of 1.2 kPa. Selection guide with glycol (cool only units) Necessary information The following information is needed to select a YLCA water chiller: 1. Cooling capacity needed.
0.27 % BY WEIGHT 35 0.26 GLYCOL FACTOR IN RECOMMENDED CONCENTRATIONS 30 0.25 RECOMMENDED CONCENTRATION % BY WEIGHT 25 0.24 20 0.23 15 10 FREEZING POINT 5 0 -10 0.30 0.29 0.28 0.27 50% 0.26 40% 0.25 30% 0.24 20% 10% 0% GLYCOL FACTOR 0.28 40 Fig. 4 - Propylene glycol in other concentrations GLYCOL FACTOR 45 GLYCOL FACTOR l/s °C/kW IN RECOMMENDED CONCENTRATIONS Fig. 1 - Recommended ethylene glycol concentrations 0.
Installation instructions Inspection Upon reception, inspect the goods and notify the carrier and the insurance company, in writing, of any possible damage during transportation. Environmental protection Packing Packing is made of recyclable material. Its elimination should be carried out in accordance with local regulations on selective collection of residual material. Refrigerant Contains greenhouse effect fluorided gas covered by the Kyoto protocol.
Location Before locating the unit, make sure you have received the appropriate product by checking the specifications described on the outside of same. The unit should be placed on a perfectly horizontal plane, making sure the base can support the weight of the unit. If vibration-free operation is required, the unit can be placed on a cork or similar anti-vibratory base, or fastened to the base with anti-vibratory plates or supports. Location of several units Avoid the recirculation of air between units.
Wiring Electrical connections All established national regulations should be complied. Each unit is supplied with a control box to which the power supply will be connected through a fused main switch or an automatic switch. WARNING order detector, when starting the equipment make sure the rotational direction is correct. If it is not correct: - The compressor does not compress. - It makes a strange sound. - Amperage consumption is limited. - It overheats in excess.
General dimensions mm and hydraulic connections 762 YLCA/YLHA PLUS 5 47 WATER INTAKE 1”G 17.5 80 32 55 WATER OUTLET 1”G DRAIN CONNECTION EXT. Ø 15 31 905 90 405 Ø 11.5 323 10 66 66 440 460 430 152 10 47 WATER INTAKE 1”G 55 32 17.5 80 WATER OUTLET 1”G 31 405 905 90 DRAIN CONNECTION EXT. Ø 15 Ø 11.
General dimensions mm and hydraulic connections 1270 1238 YLCA/YLHA PLUS 12 and 15 26 55 675 WATER INTAKE 1”G 17.5 32 90 WATER OUTLET 1”G DRAIN CONNECTION EXT.Ø 15 31 905 405 Ø 11.
General dimensions mm and hydraulic connections YLCA/YLHA PLUS 20 and 27 REAR VIEW SIDE VIEW WATER 15 OUTLET 1 1/4"GF 577 1 270 C 1 1/4"GF 15 WATER INTAKE 90 160 89 50 Ø31 WATER DRAIN 75 Ø38 D 43.5 AIR OUTLET 415 SEEN FROM ABOVE 43.
Minimum technical clearances mm ��� ��� YLCA 5, 7, 9, 12 and 15 ��� ��� ��� WATER INTAKE AND OUTLET 300 YLCA/YLHA PLUS 20 and 27 600 800 300 29
N 3 4 1 2 N L1 L1 4 2 3A Q3 1 N M2 FSC Y F2 GND NOTAS: NOTES: C2 LOAD L 0V 20 VA 230V 24 GO F1 13 12 B2 11 B3 B3 10 9 8 ��chiller 2 7 GND 6 5 2,5 bar P LP 4 D4 3 RCH 2 D2 1 GO B1 B2 B3 ID5 ID3 ID1 G GND GND Y GND ID4 ID2 14 J2 GND B1 B2 9 CONTROL ELECTRÓNICO ELECTRONIC CONTROL RESISTENCIA AUXILIAR AUXILIARY HEATER SONDA TEMPERATURA ENTRADA AGUA (NTC) WATER INTAKE TEMPERATURE PROBE (NTC) SONDA TEMPERATURA SALIDA AGUA (NTC) WATER OUTLET TEMPERATURE P
K2 6 22 (5) L N C2 LOAD Y F2 GND NOTAS: NOTES: M2 FSC 0V 20 VA 230V T 24 (SLOW) F1 315 mA (LENTO) GO F1 F1 3 14 FC (1) 11 13 11 B3 B3 12 B2 B2 11 10 9 8 ��chiller 2 10 7 GND 6 5 2,5 bar P LP 4 D4 3 RCH 2 D2 1 GO B1 B2 B3 ID5 ID3 ID1 G GND GND Y GND ID4 ID2 14 J2 GND B1 B1 9 RESISTENCIA AUXILIAR AUXILIARY HEATER SONDA TEMPERATURA ENTRADA AGUA (NTC) WATER INTAKE TEMPERATURE PROBE (NTC) SONDA TEMPERATURA SALIDA AGUA (NTC) WATER OUTLET TEMPERATURE PRO
K2 M1 3~ 4 6 22 (5) 21 (18) K3 5 1 M4 1~ 4 3 L N Y M2 FSC C3 F2 GND M3 NOTAS: NOTES: C2 LOAD 0V 20 VA 230V T 24 (SLOW) F1 315 mA (LENTO) GO F1 F1 3 14 FC (1) 11 13 12 11 10 9 8 ��chiller 2 11 7 GND 6 5 2,5 bar P LP 4 D4 3 RCH 2 D2 1 GO B1 B2 B3 ID5 ID3 ID1 G GND GND Y GND ID4 ID2 14 J2 B3 B3 B2 B2 B1 GND B1 10 SONDA TEMPERATURA ENTRADA AGUA (NTC) WATER INTAKE TEMPERATURE PROBE (NTC) SONDA TEMPERATURA SALIDA AGUA (NTC) WATER OUTLET TEMPERAT
K2 (16) K1 A2 A1 2 1 M1 3~ 4 3 6 22 (5) 5 21 L1 L2 L3 N (18) K3 Q4 4 mm2 Cu L1 L2 L3 N A2 A1 3 (12) 6 13 5 4 6 3 5 4 6 14 M4 3~ 2 1 2 2 4 1 RESISTENCIA AUXILIAR AUXILIARY HEATER SONDA TEMPERATURA ENTRADA AGUA (NTC) WATER INTAKE TEMPERATURE PROBE (NTC) SONDA TEMPERATURA SALIDA AGUA (NTC) WATER OUTLET TEMPERATURE PROBE (NTC) SONDA TEMPERATURA EXTERIOR (NTC) OUTSIDE TEMPERATURE PROBE (NTC) SONDA DE PRESIÓN RACIOMÉTRICA CONTROL VELOCIDAD VENTILADORES/ DESESCARCHES RATIOMETRI
2 4 6 K1 (16) FC (8) L1 L2 L3 A2 A1 MS Q2 Amp 2 1 M1 3~ 4 3 6 22 (5) 5 21 L1 L2 L3 N (18) K3 Q4 "B" mm2 Cu L1 L2 L3 N 400V, 3 ~,50Hz,N, L1 L2 L3 N A2 A1 (12) 4 6 14 22 6 13 21 5 4 6 3 5 M4 3~ 2 1 2 2 4 1 3 RESISTENCIA AUXILIAR AUXILIARY HEATER SONDA TEMPERATURA ENTRADA AGUA (NTC) WATER INTAKE TEMPERATURE PROBE (NTC) SONDA TEMPERATURA SALIDA AGUA (NTC) WATER OUTLET TEMPERATURE PROBE (NTC) SONDA TEMPERATURA EXTERIOR (NTC) OUTSIDE TEMPERATURE PROBE (NTC) SONDA DE PRESIÓN
Wiring YLCA/YLHA PLUS 5 to 27 YLCA TERMINAL CONNECTING STRIP MAIN SWITCH YLCA CONNECTING STRIP TERMINALS L1 N POWER SUPPLY 230V - 1 + N - ph - 50Hz SINGLE -PHASE UNITS POWER SUPPLY 400V - 3 + N - ph - 50Hz THREE-PHASE UNITS PE L1 L2 L3 N PE D1 GND FLOW SWITCH (ON UNITS WITHOUT HYDRO KIT). N5 C C5 GENERAL ALARM (VOLT-FREE INVERTER CONTACT. NO RESIST. 2A MAX. AT 230Vac). ID5 GND D2 2 N2 REMOTE ON/OFFSWITCH REMOTE COOL/HEAT SWITCH CLOSED=COOL.
Electrical characteristics Compressor Power supply V.ph.Hz. Model Start Nominal A Cool Heat YLCA 5 7.8 - YLHA PLUS 5 7.8 8.1 11.7 - 12.4 13.2 YLCA 9 17 - YLHA PLUS 9 17 14.5 YLCA 7 3.9 - YLHA PLUS 7 4.1 4.8 YLCA 9 5.7 - 6 5.8 YLCA 12 6.36 - YLHA PLUS 12 6.36 6.38 8.9 - YLHA PLUS 15 8.7 8.9 YLCA 20 13 - YLHA PLUS 20 12.2 11.7 YLCA 27 16.7 - YLHA PLUS 27 16.7 16 YLCA 7 YLHA PLUS 7 230.1.50 YLHA PLUS 9 YLCA 15 400.3.
Operating instructions µC2 (Rev. 1016) Control unit description This is a multipurpose controller specially programmed for use with air-water chillers and heat pumps equipped with a compressor with one single power stage. Main functions - Water temperature control (at intake or outlet, as per parameter r6). - Defrost cycle management. - System operating and safety management. - Fan speed control. - Alarm management. - Connection for supervision and telephone assistance (access serial connection RS485).
ALARM COMP. 1 HEATER N PUMP 4-WAY VALVE General diagram, YLCA 5, 7, 9, 12 and 15 230.1.50 ID2 OUTDOOR PROBE. STANDARD UNIT 315 mA No5 24 TRANSFORMER 230 N L 230.1.
ALARM COMP. 1 HEATER N PUMP 4-WAY VALVE General diagram, YLCA 20,27 and YLHA PLUS 5-27 230.1.50 Y GND ID4 ID2 315 mA C5 No2 No3 X No5 No4 C3/4 V+ ID1 X B4 ID3 C1/2 C1/2 C3/4 GND ID5 No1 (B4) ID5 GND GND B3 ID4 G B2 ID3 B1 ID1 G0 ID2 WATER INTAKE (B1) WATER DISCHARGE (B2) OUTDOOR PROBE (B3) L P PRESSURE PROBE RS 485 24 TRANSFORMER 230 N L 230.1.
Symbols on the display The display has three figures in green, plus a symbol and a decimal. It also shows the symbols, in amber, of the functions selected (the alarm symbol is red).
Location of controls FAN FLOW SWITCH (FS) EXCHANGER OUTDOOR NTC PROBE (YLCA/YLHA PLUS 5 to 15) (B3) OUTDOOR TEMPERATURE PROBE YLCA/YLHA PLUS 5 to 15 WITH LAK (B3) YLCA/YLHA PLUS 5 to 15 STANDARD (B4) YLCA/YLHA PLUS 20 to 27 STANDARD (B3) PRESSURE PROBE (BA) (YLCA/YLHA PLUS 5 to 20 LAK; YLCA/YLHA PLUS 20 to 27) WATER DISCHARGE NTC PROBE (B2) INDOOR EXCHANGER INDOOR EXCHANGER 4-WAY VALVE WATER INTAKE NTC PROBE (B1) LOW PRESSURE SWITCH (LP) HIGH PRESSURE SWITCH (HP) COMPRESSOR Parameter tables The
Parameters related to the probes Display Description Level VS Unit Max. Min. Value /01 NTC B1 probe (water intake); 0=absent (function not available). 1=present F 1 (R/W) - 1 0 1 /02 NTC B2 probe (water outlet). 0=absent (function not available). 1=present F 2 (R/W) - 1 0 1 /03 NTC B3 probe . 1=condensation probe. 2=outdoor probe. F 14 (R/W) - 1 0 (a) /04 Probe type B4. 0=absent. 1=ON/OFF. 2=outdoor NTC probe. 3=ratiometric 5Vdc.
Minimum operating time of a compressor ON SIGNAL OFF t ON COMPRESSOR t C1 OFF Minimum OFF time of a compressor ON SIGNAL OFF t ON COMPRESSOR t C2 OFF Minimum time between compressor start-ups ON SIGNAL OFF t ON COMPRESSOR C3 t OFF 43
Compressor/pump OFF delays ON COMPRESSOR OFF t ON PUMP C8 t OFF Pump/compressor start-up delays ON PUMP OFF t ON COMPRESSOR C7 44 t OFF
Parameters related to the fans Display Level VS F01 Fan outlet. 0=absent (function not available); 1=present Description F F02 Operating mode: 0 = always ON (function not available) 1 = Parallel with compressor (function not available) 2 = ON/OFF operation (function not available) 3 = Parallel with compressor and speed adjustment. F03 Unit Max. Min.
Parameters related to defrost Display Description Level VS Unit Max. Min. Value d01 Execution of defrost 0= no (function not available) 1= yes. U 7 (R/W) - 1 0 1 d02 Time or temperature defrost. 0= time (function not available). 1= temperature / pressure U 8 (R/W) - 1 0 1 d03 Defrost start temperature / pressure U 19 (R/W) °C bar d04 -40/ 11 -3 6.2 d04 Defrost end temperature / pressure U 21 (R/W) °C bar 80/ 12 d03 20 14.
Parameters related to defrost control configuration Display Description Level VS Unit Max. Min. Value A01 Antifreeze control set point temperature U 11 (R/W) °C - A07 3 A02 Antifreeze reset differential U 12 (R/W) °K 50 0.3 5 A03 Antifreeze alarm bypass time U 22 (R/W) sec. 150 0 0 A04 Antifreeze heater activation temperature U 13 (R/W) °C r16 A01 3 A05 Antifreeze heater activation differential U 14 (R/W) °K 50 0.
Parameters for unit configuration Display 48 Description Level VS Unit Max. Min. Value H01 Unit model. 2= air-water intake; 3= air-water heat pump. F 54 (R/W) 2 (YLCA) 3 (YLHA PLUS) H02 Number of vent circuits (do not modify this parameter) F 12 (R/W) 0 H03 No. of evaporating units present (do not modify this parameter) F 13 (R/W) 0 H04 No.
Parameters for alarm configuration Display Description Level VS Unit Max. Min. Value P01 Alarm delay by flow switch at start-up. U 63 (R/W) sec. 150 0 20 P02 Alarm delay by flow switch with unit in operation. U 64 (R/W) sec. 120 0 5 P03 Alarm delay by low pressure switch at start-up. U 65 (R/W) sec. 200 0 60 P05 Alarm reset 6= Low and high pressure switch manual reset at third activation in one hour. Antifreeze control is manual reset.
Parameters for regulator configuration Display Level VS Unit Max. Min. Value r01 Description Cool cycle set point temperature U 41 (R/W) °C r14 r13 12 r02 Cool set point temperature differential U 42 (R/W) °C 50 0.3 1 r03 Heat cycle set point temperature U 43 (R/W) °C r16 r15 40 r04 Heat cycle set point temperature differential U 44 (R/W) °C 50 0.3 2 r06 Type of adjustment 0= Proportional. Intake temperature. 1= Proportional + neutral zone. Intake temp.
Table of alarms Display Alarm type Reset A1 Antifreeze alarm AHt High temp. at start-up (if activated. P20=1) Automatic ALt Low temp. at start-up (if activated. P20=1) Automatic d1-2 Defrost in operation dF1-2 Manual - Problem in defrost Automatic E1 Probe B1 Automatic E2 Probe B2 Automatic E3 Probe B3 Automatic E4 Probe B4 Automatic ELS Low supply voltage Automatic EHS High supply voltage Automatic EPr Eprom error. Unit in operation. Automatic EPb Eprom error.
Temperature/resistance characteristics of the NTC control probes (10 kOhms) Temperature (°C) Resistance (kOhms) Temperature (°C) Resistance (kOhms) Temperature (°C) Resistance (kOhms) Temperature (°C) Resistance (kOhms) -50 329.20 -16 55.95 26 9.63 68 2.36 -49 310.70 -15 53.99 27 9.28 69 2.29 -14 50.90 28 8.94 70 2.22 -48 293.30 -13 48.66 29 8.82 71 2.16 -47 277.00 -12 46.48 30 8.31 72 2.10 -46 261.80 -11 44.41 31 6.01 73 2.04 -45 247.50 -10 42.
Accessories Remote terminal This accessory allows remote control and supervision of the air conditioning unit (up to 1040 m.). Functions are the same as the standard control panel keyboard. This remote terminal is compatible with said keyboard, and the air conditioning unit can be accessed from both devices. For this application, it must be connected to the system by means of the RS485 serial line connection accessory.
PRG mute clear SEL Set Sel Prg RS485 TELEPHONE CABLE Max. L.= 40m G+GND RS485 G 8 G0 Max. L = 1000m 24Vac RJ12 Power supply RJ12 Power supply 2 stranded cables with shielding AWG22 (0.35 mm2 ) Rx/Tx+. Rx/Tx-. Gnd In lenghts of over 200 m. Insert a 120 ��resistor between Tx/Rx+ and Tx/Rx-.
Connecting serial line RS485 This accessory allows connecting the air conditioning unit to a serial line RS485 supervision network. It must also be used to install the remote terminal accessory. Mounting Connect the accessory to the four-pole socket base at the lower right angle of the module with display and keyboard. Use the 4-cable connector supplied. Connect to the supervising system as indicated in the drawing below.
Remote control unit Wall-mounted, with keys for COOL/HEAT and ON/OFF functions. Includes voltage, alarm and COOL/HEAT LEDs. Prior to installation, value 1 must be given to parameters H06 and H07. 1 123456- Voltage LED Alarm LED ON/OFF selection button Unit ON LED COOL/HEAT selection button LED on in heat function/ LED off in cool function. 2 ! 3 6 5 REMOTE CONTROL - The remote control unit can be located at a maximum distance of 50 m. - Minimum cable section should be 0.35 mm2.
Buffer Tank YLCA/YLHA PLUS 5, 7, 9, 12 and 15 polyethylene and an a coat of embossed aluminium. There For installations with small water volumes in wich it is necessary to increase thermal inertia. The installation of this unit achieves greater pressure in the water temperature of the installation and lowers the on/off cycles of the compressor. Casing Made up of screwed-on detachable panels that give access to the internal components.
Mounting on 5, 7 and 9 units DETAIL "A" WATER INTAKE FLEXIBLE HOSE WATER DISCHARGE Mounting on 12 and 15 units DETAIL "A" WATER INTAKE FLEXIBLE HOSE WATER DISCHARGE 1. Fasten the buffer tank to the unit (Detail A) by means of the screws supplied with the accessory. 2. Hydraulically interconnect the buffer tank to the unit by means of the flexible hose, the two other hoses and the two Curalite gaskets supplied with the accessory. Cover the hose with isolation.
WIRING OF THE HEATER (See wiring diagram of the unit) POWER SUPPLY MAGNETOTHERMAL HEATER PROTECTION (Q1) 1 2 3 N1 N2 N3 HEATER CONNECTING CABLE TO CONTROL PANEL (INCLUDED WITH THE ACCESSORY) CONNECTING BOX CONNECTING BOX 230M 400T HEATER CONTACT HEATER CONTACT A1 HEATER POWER SUPPLY CABLE (NOT INCLUDED WITH THE ACCESSORY) A1 1 3 5 13 1 (K2) 2 4 HEATER CABLE mm2 Cu Q1 (A) 2.5 15 3 kW/230M 2.5 15 3 kW/400T 1.5 6 4.5 kW/400T 1.5 8 6 kW/400T 2.
115 Litre Buffer Tank for YLCA/YLHA PLUS 20 coated with 10 mm, thick, closed cell, reticulated and expanded polyethylene, and a coat of embossed aluminium. At and 27 Adequate for installations with low water volume and need to have increased thermal inertia. This application achieves improved water temperature in the installation and decreases the on and off cycles of the compressor. Casing Made up of screwed-on detachable panels that give access to the internal components.
Hydraulic connections YLCA/YLHA PLUS 20 and 27 N1 N3 N2 N1. Interconnecting tubing (must be insulated to avoid condensation) N2. Water outlet. N3. Water intake.
Wiring of the heater - Prior to installation, power off the YLHA PLUS units. - Do not power on again until installation is finished and with the tank full of water. AH - 10.5 Kw backup heater (400.3.50). BT - Buffer tank. EBBT - Buffer tank connections box. EBHP - YLHA PLUS connections box. K2 - Heater contactor. Q1 - Thermomagnetic protector of the heater. Installation N1 - Remove the top cover of the tank. N2 - Remove the cover of the connections box.
High pressure fan YLCA/YLHA PLUS 5-27 their connecting points on the control box. 2. Replace the standard fan condenser with the condenser supplied with the accessory. 3. Remove the standard fan from its housing. Save the screws and rubber supports. 4. Fit the high pressure fan 1 , inserting the duct nozzle 2 between the supporting panel and the fan grid. Replace the same rubber supports 4 and screws 3 . See enclosed diagram. 5.
Units 12 and 15 2 1 4 3 C2 C3 LOCATION OF CONDENSER Units 20 and 27 C2 C3 LOCATION OF CONDENSER 2 1 3 4 64
Low ambient temperature kit (ratiometric pressure transducer) YLCA 5-15 Attention: Install the kit with power supply to the unit turned off. To adjust condensing pressure at low ambient temperatures (down to -18° C). Mounting pressure transducer on the cooling circuit Screw the ratiometric transducer on to the free Schrader valve located on the liquid line (YLCA). Check for leaks. The kit is comprised of: 1 ratiometric pressure transducer. 1 Packard connector. 1 three-way connector.
Tray heater YLHA PLUS 5-15 This flexible cable heater can be used in cold climates to avoid the forming of ice and the subsequent obstruction at the tray drain of the heat pumps. This accessory includes: 1 Flexible cable heater with a thermostat. 2 m, of 50 mm, self-adhesive aluminium tape. Heater characteristics Current: 230.1.
Compressor heater YLHA PLUS 5 - 15 Assembly 2 K1 22 - LENGTHEN THE HEATER CABLES. IF NECESSARY CH 40 220/240-1-50 (70 W) 1 21 K1 22 CH 220/240-1-50 70W 2 CH - COMPRESSOR HEATER K1 - COMPRESSOR CONTACTOR CH 240-1-50 70W All data and measurements are subject to change without prior notice.
www.johnsoncontrols.