Technical Guide

251933-YTG-V-0913
104 Johnson Controls Unitary Products
060
(5.0)
208-1-60 26.2 134.0 41.0 2.3 7.6 10.0
None - - - 52.7 70
E05 4.0 1 19.2 76.7 90
E07 5.6 1 26.9 86.3 100
E10 8.0 1 38.5 100.7 110
E15 11.9 2 57.2 124.2 125
E20 15.9 2 76.4 148.2 150
E30 22.2 2 106.7 186.1 200
230-1-60 26.2 134.0 41.0 2.3 7.6 10.0
None - - - 52.7 70
E05 5.3 1 22.1 80.3 100
E07 7.5 1 31.3 91.7 110
E10 10.6 1 44.2 107.9 110
E15 15.9 2 66.3 135.5 150
E20 21.2 2 88.3 163.1 175
E30 29.6 2 123.3 206.8 225
208-3-60 15.6 110.0 24.4 2.3 7.6 10.0
None - - - 39.4 50
E05 4.0 1 11.1 53.3 60
E07 5.6 1 15.5 58.8 70
E10 8.0 1 22.2 67.2 70
E15 11.9 2 33.0 80.7 90
E20 15.9 2 44.1 94.6 100
E30 22.2 2 61.6 116.4 125
230-3-60 15.6 110.0 24.4 2.3 7.6 10.0
None - - - 39.4 50
E05 5.3 1 12.7 55.3 60
E07 7.5 1 18.0 62.0 70
E10 10.6 1 25.5 71.3 80
E15 15.9 2 38.2 87.2 90
E20 21.2 2 51.0 103.1 110
E30 29.6 2 71.2 128.4 150
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XP036-060 (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps