Technical Guide

251933-YTG-V-0913
20 Johnson Controls Unitary Products
ZF/ZR/XP036-060 Unit Limitations
Size
(Tons)
Unit Voltage
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (°F)
ZF/ZR/XP036
(3.0)
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125
ZF/ZR/XP048
(4.0)
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125
ZF/ZR/XP060
(5.0)
208/230-1-60 187 252 125
208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125
ZF072
(6.0)
208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125