Technical Guide

251933-YTG-V-0913
44 Johnson Controls Unitary Products
115°F 125°F
1000
77 43.6 4.2 16.5 15.6 11.5 - - - 41.0 4.6 14.7 12.6 9.7 - - -
72 39.9 4.2 25.9 21.8 17.7 13.7 - - 37.3 4.6 24.1 20.1 16.0 12.0 - -
67 36.1 4.1 35.2 28.0 23.9 19.9 15.8 - 33.6 4.5 33.6 26.4 22.3 18.3 14.2 -
62 33.1 4.1 33.1 33.1 26.4 22.3 18.2 14.2 31.1 4.5 31.1 31.1 23.3 19.3 15.2 11.1
1200
77 44.6 4.2 22.5 17.7 12.8 - - - 41.4 4.6 21.5 15.8 10.9 - - -
72 40.7 4.2 29.4 24.6 19.7 14.9 - - 37.7 4.6 27.7 22.9 18.0 13.2 - -
67 36.9 4.1 36.3 31.5 26.6 21.8 17.0 - 33.9 4.6 33.9 29.9 25.1 20.3 15.4 -
62 33.9 4.1 33.9 33.9 29.4 24.5 19.7 14.9 31.5 4.5 31.5 31.5 26.2 21.4 16.6 11.7
57 34.4 4.1 34.4 34.4 29.8 25.0 20.1 15.3 31.9 4.6 31.9 31.9 26.6 21.8 16.9 12.1
1400
77 45.5 4.2 28.5 19.7 14.1 - - - 41.9 4.7 28.2 19.0 12.2 - - -
72 41.6 4.2 32.9 27.3 21.7 16.1 - - 38.1 4.6 31.3 25.6 20.0 14.4 - -
67 37.7 4.1 37.4 34.9 29.3 23.7 18.1 - 34.3 4.6 34.3 33.5 27.9 22.3 16.7 -
62 34.6 4.1 34.6 34.6 32.3 26.7 21.1 15.5 31.8 4.5 31.8 31.8 29.2 23.6 18.0 12.3
57 35.1 4.1 35.1 35.1 32.8 27.2 21.6 16.0 32.2 4.6 32.2 32.2 29.6 24.0 18.3 12.7
1600
77 46.5 4.2 34.5 21.8 15.4 - - - 42.3 4.7 35.0 22.2 13.4 - - -
72 42.5 4.2 36.5 30.1 23.7 17.4 - - 38.5 4.6 34.8 28.4 22.0 15.7 - -
67 38.5 4.2 38.5 38.4 32.0 25.7 19.3 - 34.6 4.6 34.6 34.6 30.7 24.3 17.9 -
62 35.3 4.1 35.3 35.3 35.3 29.0 22.6 16.2 32.1 4.6 32.1 32.1 32.1 25.7 19.3 13.0
57 35.9 4.1 35.9 35.9 35.9 29.5 23.1 16.8 32.5 4.6 32.5 32.5 32.5 26.2 19.8 13.4
1800
72 43.3 4.2 39.6 32.6 25.6 18.6 - - 39.1 4.6 37.6 30.6 23.6 16.7 - -
67 39.2 4.2 39.2 39.1 34.5 27.5 20.5 - 35.2 4.6 35.2 35.2 32.9 25.9 18.9 -
62 36.0 4.1 36.0 36.0 36.0 29.0 22.0 15.0 32.6 4.6 32.6 32.6 32.6 25.6 18.6 11.7
57 36.5 4.2 36.5 36.5 36.5 29.5 22.5 15.5 33.0 4.6 33.0 33.0 33.0 26.1 19.1 12.1
2000
72 44.0 4.2 42.7 35.0 27.4 19.7 - - 39.7 4.6 39.7 32.9 25.3 17.7 - -
67 39.9 4.2 39.9 39.9 37.0 29.3 21.7 - 35.7 4.6 35.7 35.7 35.2 27.6 20.0 -
62 36.6 4.1 36.6 36.6 36.6 29.0 21.3 13.7 33.1 4.6 33.1 33.1 33.1 25.5 17.9 10.3
57 37.2 4.2 37.2 37.2 37.2 29.5 21.9 14.2 33.6 4.6 33.6 33.6 33.6 26.0 18.4 10.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP048 (4.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65