Technical Guide

251933-YTG-V-0913
Johnson Controls Unitary Products 67
060
(5.0)
208-3-60
14.1 88.0 22.0 2.3 8.2 0.0
None - - - 28.1 35
E05 4.0 1 11.1 28.1 35
E07 5.6 1 15.5 29.7 40
E10 8.0 1 22.2 38.0 40
E15 11.9 2 33.0 51.5 60
E20 15.9 2 44.1 65.4 70
E30 22.2 2 61.6 87.3 90
230-3-60
14.1 88.0 22.0 2.3 8.2 0.0
None - - - 28.1 35
E05 5.3 1 12.7 28.1 35
E07 7.5 1 18.0 32.8 40
E10 10.6 1 25.5 42.1 45
E15 15.9 2 38.2 58.1 60
E20 21.2 2 51.0 74.0 80
E30 29.6 2 71.2 99.3 100
460-3-60
7.7 55.0 12.0 1.3 4.1 0.0
None - - - 15.0 20
E07 6.8 1 8.2 15.3 20
E10 10.1 1 12.1 20.3 25
E15 13.6 2 16.4 25.6 30
E20 19.5 2 23.5 34.4 35
E30 28.8 2 34.6 48.4 50
575-3-60
4.8 36.0 7.5 1.3 3.6 0.0
None - - - 10.6 15
E10 10.6 1 10.2 17.2 20
E15 15.9 1 15.3 23.6 25
E20 21.2 2 20.4 30.0 30
E30 30.4 2 29.3 41.1 45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF036-060 (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps