Technical Guide

251933-YTG-V-0913
Johnson Controls Unitary Products 73
060
(5.0)
208-1-60 26.4 134.0 41.2 2.3 7.6 0.0
None - - - 42.9 60
E05 4.0 1 19.2 42.9 60
E07 5.6 1 26.9 43.2 60
E10 8.0 1 38.5 57.6 60
E15 11.9 2 57.2 81.0 90
E20 15.9 2 76.4 105.1 110
E30 22.2 2 106.7 142.9 150
230-1-60 26.4 134.0 41.2 2.3 7.6 0.0
None - - - 42.9 60
E05 5.3 1 22.1 42.9 60
E07 7.5 1 31.3 48.6 60
E10 10.6 1 44.2 64.7 70
E15 15.9 2 66.3 92.3 100
E20 21.2 2 88.3 119.9 125
E30 29.6 2 123.3 163.7 175
208-3-60 15.9 110.0 24.9 2.3 5.2 0.0
None - - - 27.4 35
E05 4.0 1 11.1 27.4 35
E07 5.6 1 15.5 27.4 35
E10 8.0 1 22.2 34.3 40
E15 11.9 2 33.0 47.8 50
E20 15.9 2 44.1 61.7 70
E30 22.2 2 61.6 83.5 90
230-3-60 15.9 110.0 24.9 2.3 5.2 0.0
None - - - 27.4 35
E05 5.3 1 12.7 27.4 35
E07 7.5 1 18.0 29.1 35
E10 10.6 1 25.5 38.4 40
E15 15.9 2 38.2 54.3 60
E20 21.2 2 51.0 70.2 80
E30 29.6 2 71.2 95.5 100
460-3-60 7.7 52.0 12.1 1.3 2.6 0.0
None - - - 13.5 20
E07 6.8 1 8.2 13.5 20
E10 10.1 1 12.1 18.4 20
E15 13.6 2 16.4 23.7 25
E20 19.5 2 23.5 32.6 35
E30 28.8 2 34.6 46.6 50
575-3-60 5.7 38.9 8.9 1.3 2.0 0.0
None - - - 10.2 15
E10 10.6 1 10.2 15.2 20
E15 15.9 1 15.3 21.6 25
E20 21.2 2 20.4 28.0 30
E30 30.4 2 29.3 39.1 40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZR036-060 (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps