Technical Guide

251933-YTG-V-0913
Johnson Controls Unitary Products 81
060
(5.0)
208-3-60 15.6 110.0 24.4 2.3 8.2 0.0
None - - - 30.0 40
E05 4.0 1 11.1 43.9 50
E07 5.6 1 15.5 49.4 60
E10 8.0 1 22.2 57.8 60
E15 11.9 2 33.0 71.3 80
E20 15.9 2 44.1 85.2 90
E30 22.2 2 61.6 107.0 110
230-3-60 15.6 110.0 24.4 2.3 8.2 0.0
None - - - 30.0 40
E05 5.3 1 12.7 45.9 50
E07 7.5 1 18.0 52.6 60
E10 10.6 1 25.5 61.9 70
E15 15.9 2 38.2 77.8 80
E20 21.2 2 51.0 93.7 100
E30 29.6 2 71.2 119.0 125
460-3-60 7.7 52.0 12.1 1.3 4.1 0.0
None - - - 15.0 20
E07 6.8 1 8.2 25.2 30
E10 10.1 1 12.1 30.2 35
E15 13.6 2 16.4 35.5 40
E20 19.5 2 23.5 44.3 45
E30 28.8 2 34.6 58.3 60
575-3-60 5.8 38.9 9.1 1.3 3.6 0.0
None - - - 11.9 15
E10 10.6 1 10.2 24.6 25
E15 15.9 1 15.3 31.0 35
E20 21.2 2 20.4 37.4 40
E30 30.4 2 29.3 48.5 50
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XP036-060 (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps