Technical Guide

251933-YTG-V-0913
Johnson Controls Unitary Products 91
060
(5.0)
208-1-60 21.1 105.0 33.0 2.3 7.6 10.0
None - - - 46.3 60
E05 4.0 1 19.2 46.3 60
E07 5.6 1 26.9 55.7 60
E10 8.0 1 38.5 70.1 80
E15 11.9 2 57.2 93.5 100
E20 15.9 2 76.4 117.6 125
E30 22.2 2 106.7 155.4 175
230-1-60
21.1 105.0 33.0 2.3 7.6 10.0
None - - - 46.3 60
E05 5.3 1 22.1 49.6 60
E07 7.5 1 31.3 61.1 70
E10 10.6 1 44.2 77.2 80
E15 15.9 2 66.3 104.8 110
E20 21.2 2 88.3 132.4 150
E30 29.6 2 123.3 176.2 200
208-3-60
14.1 88.0 22.0 2.3 7.6 10.0
None - - - 37.5 50
E05 4.0 1 11.1 37.5 50
E07 5.6 1 15.5 41.4 50
E10 8.0 1 22.2 49.8 50
E15 11.9 2 33.0 63.3 70
E20 15.9 2 44.1 77.2 80
E30 22.2 2 61.6 99.0 100
230-3-60
14.1 88.0 22.0 2.3 7.6 10.0
None - - - 37.5 50
E05 5.3 1 12.7 37.9 50
E07 7.5 1 18.0 44.6 50
E10 10.6 1 25.5 53.9 60
E15 15.9 2 38.2 69.8 70
E20 21.2 2 51.0 85.7 90
E30 29.6 2 71.2 111.0 125
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF036-060 (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps