Technical Guide

251933-YTG-V-0913
94 Johnson Controls Unitary Products
060
(5.0)
208-1-60 26.4 134.0 41.2 2.3 7.6 10.0
None - - - 52.9 70
E05 4.0 1 19.2 52.9 70
E07 5.6 1 26.9 55.7 70
E10 8.0 1 38.5 70.1 80
E15 11.9 2 57.2 93.5 100
E20 15.9 2 76.4 117.6 125
E30 22.2 2 106.7 155.4 175
230-1-60 26.4 134.0 41.2 2.3 7.6 10.0
None - - - 52.9 70
E05 5.3 1 22.1 52.9 70
E07 7.5 1 31.3 61.1 70
E10 10.6 1 44.2 77.2 80
E15 15.9 2 66.3 104.8 110
E20 21.2 2 88.3 132.4 150
E30 29.6 2 123.3 176.2 200
208-3-60 15.9 110.0 24.9 2.3 5.2 10.0
None - - - 37.4 45
E05 4.0 1 11.1 37.4 45
E07 5.6 1 15.5 38.4 50
E10 8.0 1 22.2 46.8 50
E15 11.9 2 33.0 60.3 70
E20 15.9 2 44.1 74.2 80
E30 22.2 2 61.6 96.0 100
230-3-60 15.9 110.0 24.9 2.3 5.2 10.0
None - - - 37.4 45
E05 5.3 1 12.7 37.4 45
E07 7.5 1 18.0 41.6 50
E10 10.6 1 25.5 50.9 60
E15 15.9 2 38.2 66.8 70
E20 21.2 2 51.0 82.7 90
E30 29.6 2 71.2 108.0 110
460-3-60 7.7 52.0 12.1 1.3 2.6 5.0
None - - - 18.5 25
E07 6.8 1 8.2 19.7 25
E10 10.1 1 12.1 24.7 25
E15 13.6 2 16.4 29.9 30
E20 19.5 2 23.5 38.8 40
E30 28.8 2 34.6 52.8 60
575-3-60 5.7 38.9 8.9 1.3 2.0 4.0
None - - - 14.2 15
E10 10.6 1 10.2 20.2 25
E15 15.9 1 15.3 26.6 30
E20 21.2 2 20.4 33.0 35
E30 30.4 2 29.3 44.1 45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZR036-060 (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps