User's Manual

1068152-YTG-L-0815
110 Johnson Controls Unitary Products
09
(8.5)
208-3-60 14.5 98 23 14.5 98 23 2.3 7 1.1
None - - - 44.2 45 50 47 275 46.4 50 50 49 285
11725 12 1 33.3 50.4 60 60 47 275 53.1 60 60 49 285
12525 18.6 1 51.6 73.3 80 80 67 275 76 80 80 70 285
13225 24 1 66.6 92 100 100 85 275 94.8 100 100 87 285
14225 31.8 2 88.3 119.1 125 125 110 275 121.9 125 125 112 285
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1
None - - - 44.4 45 50 47 278 46.4 50 60 49 272
11725 16 1 38.5 57.1 60 60 53 278 59.6 60 60 55 272
12525 24.8 1 59.7 83.6 90 90 77 278 86.1 90 90 79 272
13225 32 1 77 105.3 110 110 97 278 107.8 110 110 99 272
14225 42.4 2 102 136.5 150 150 126 278 139 150 150 128 272
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5
None - - - 20.4 25 25 22 153 21.4 25 25 23 149
11746 16.5 1 19.8 29.3 30 30 27 153 30.5 35 27 28 149
12846 27.8 1 33.4 46.3 50 50 43 153 47.5 50 43 44 149
13346 33 1 39.7 54.1 60 60 50 153 55.4 60 50 51 149
14246 41.7 2 50.2 67.3 70 70 62 153 68.5 70 62 63 149
575-3-60 6 41 9 6 41 9 1.1 2.5 0.4 None - - - 18.2 20 20 19 109 19 20 20 20 106
12
(10)
208-3-60 16 110 25 15.6 110 24 2.3 9.9 1.1
None - - - 50.1 60 60 53 312 52.3 60 60 56 322
11725 12 1 33.3 54 60 60 53 312 56.8 60 60 56 322
12525 18.6 1 51.6 76.9 80 80 71 312 79.6 80 80 73 322
13225 24 1 66.6 95.6 100 100 88 312 98.4 100 100 91 322
14225 31.8 2 88.3 122.8 125 125 113 312 125.5 150 150 115 322
230-3-60 16 110 25 15.6 110 24 2.3 9.4 1
None - - - 49.6 50 60 52 321 51.6 60 60 55 315
11725 16 1 38.5 59.9 60 60 55 321 62.4 70 70 57 315
12525 24.8 1 59.7 86.4 90 90 79 321 88.9 90 90 82 315
13225 32 1 77 108 110 110 99 321 110.5 125 125 102 315
14225 42.4 2 102 139.3 150 150 128 321 141.8 150 150 130 315
460-3-60 7.8 52 12 7.8 52 12 1.3 4.7 0.5
None - - - 24.9 25 30 26 156 25.9 30 30 27 152
11746 16.5 1 19.8 30.6 35 35 28 156 31.9 35 28 29 152
12846 27.8 1 33.4 47.6 50 50 44 156 48.9 50 44 45 152
13346 33 1 39.7 55.5 60 60 51 156 56.8 60 51 52 152
14246 41.7 2 50.2 68.6 70 70 63 156 69.9 70 63 64 152
575-3-60 5.7 38.9 9 5.8 38.9 9 1.1 4.3 0.4 None - - - 19.5 20 25 21 127 20.3 25 25 22 124
14
(12.5)
208-3-60 19.6 136 31 19.6 136 31 5.8 9.9 1.1
None - - - 59.8 60 70 63 367 62 70 80 66 377
11725 12 1 33.3 59.8 60 70 63 367 62 70 80 66 377
12525 18.6 1 51.6 76.9 80 80 71 367 79.6 80 80 73 377
13225 24 1 66.6 95.6 100 100 88 367 98.4 100 100 91 377
14225 31.8 2 88.3 122.8 125 125 113 367 125.5 150 150 115 377
230-3-60 19.6 136 31 19.6 136 31 5.2 9.4 1
None - - - 58.7 60 70 62 372 60.7 70 80 64 376
11725 16 1 38.5 59.9 60 70 62 372 62.4 70 80 64 376
12525 24.8 1 59.7 86.4 90 90 79 372 88.9 90 90 82 376
13225 32 1 77 108 110 110 99 372 110.5 125 125 102 376
14225 42.4 2 102 139.3 150 150 128 372 141.8 150 150 130 376
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 4.7 0.5
None - - - 26.1 30 30 28 184 27.1 30 30 29 186
11746 16.5 1 19.8 30.6 35 35 28 184 31.9 35 28 29 186
12846 27.8 1 33.4 47.6 50 50 44 184 48.9 50 44 45 186
13346 33 1 39.7 55.5 60 60 51 184 56.8 60 51 52 186
14246 41.7 2 50.2 68.6 70 70 63 184 69.9 70 63 64 186
575-3-60 6.6 55.3 10 6.6 55.3 10 2.2 4.3 0.4 None - - - 21.4 25 25 23 162 22.2 25 25 24 164
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.
ZX04-14 Medium Static Indoor Blower - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Nominal
Unit
Voltage
Compressor 1 Compressor 2
OD
Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat
Field Installed Kit
2EK045*
MCA
1
(Amps)
Min
Fuse
2
/
Breaker
3
Size
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
Min
Discon-
nect
Rating
4
MCA
1
w/Pwr
Exh
(Amps)
Min
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Max
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Min
Discon-
nect
Rating
4
/
Pwr Exh
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA