User's Manual

1068152-YTG-L-0815
118 Johnson Controls Unitary Products
12
(10)
208-3-60 16 110 25 15.6 110 24 2.3 13.5 1.1
None - - - 53.7 60 60 57 342 55.9 60 70 60 352
11725 12 1 33.3 58.5 60 60 57 342 61.3 70 70 60 352
12525 18.6 1 51.6 81.4 90 90 75 342 84.1 90 90 77 352
13225 24 1 66.6 100.1 110 110 92 342 102.9 110 110 95 352
14225 31.8 2 88.3 127.3 150 150 117 342 130 150 150 120 352
230-3-60 16 110 25 15.6 110 24 2.3 13.4 1
None - - - 53.6 60 60 57 342 55.6 60 70 59 337
11725 16 1 38.5 64.9 70 70 60 342 67.4 70 70 62 337
12525 24.8 1 59.7 91.4 100 100 84 342 93.9 100 100 86 337
13225 32 1 77 113 125 125 104 342 115.5 125 125 106 337
14225 42.4 2 102 144.3 150 150 133 342 146.8 150 150 135 337
460-3-60 7.8 52 12 7.8 52 12 1.3 6.7 0.5
None - - - 26.9 30 30 29 167 27.9 30 30 30 163
11746 16.5 1 19.8 33.1 35 35 30 167 34.4 35 30 32 163
12846 27.8 1 33.4 50.1 60 60 46 167 51.4 60 46 47 163
13346 33 1 39.7 58 60 60 53 167 59.3 60 53 55 163
14246 41.7 2 50.2 71.1 80 80 65 167 72.4 80 65 67 163
575-3-60 5.7 38.9 9 5.8 38.9 9 1.1 5.4 0.4 None - - - 20.6 25 25 22 127 21.4 25 25 23 124
14
(12.5)
208-3-60 19.6 136 31 19.6 136 31 5.8 13.5 1.1
None - - - 63.4 70 80 67 397 65.6 70 80 70 407
11725 12 1 33.3 63.4 70 80 67 397 65.6 70 80 70 407
12525 18.6 1 51.6 81.4 90 90 75 397 84.1 90 90 77 407
13225 24 1 66.6 100.1 110 110 92 397 102.9 110 110 95 407
14225 31.8 2 88.3 127.3 150 150 117 397 130 150 150 120 407
230-3-60 19.6 136 31 19.6 136 31 5.2 13.4 1
None - - - 62.7 70 80 66 393 64.7 70 80 69 398
11725 16 1 38.5 64.9 70 80 66 393 67.4 70 80 69 398
12525 24.8 1 59.7 91.4 100 100 84 393 93.9 100 100 86 398
13225 32 1 77 113 125 125 104 393 115.5 125 125 106 398
14225 42.4 2 102 144.3 150 150 133 393 146.8 150 150 135 398
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 6.7 0.5
None - - - 28.1 30 35 30 194 29.1 30 35 31 196
11746 16.5 1 19.8 33.1 35 35 30 194 34.4 35 30 32 196
12846 27.8 1 33.4 50.1 60 60 46 194 51.4 60 46 47 196
13346 33 1 39.7 58 60 60 53 194 59.3 60 53 55 196
14246 41.7 2 50.2 71.1 80 80 65 194 72.4 80 65 67 196
575-3-60 6.6 55.3 10 6.6 55.3 10 2.2 5.4 0.4 None - - - 22.5 25 25 24 162 23.3 25 25 25 164
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.
ZX04-14 Hi Static Indoor Blower - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Nominal
Unit
Voltage
Compressor 1 Compressor 2
OD
Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat
Field Installed Kit
2EK045*
MCA
1
(Amps)
Min
Fuse
2
/
Breaker
3
Size
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
Min
Discon-
nect
Rating
4
MCA
1
w/Pwr
Exh
(Amps)
Min
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Max
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Min
Discon-
nect
Rating
4
/
Pwr Exh
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA