User's Manual

1068152-YTG-L-0815
122 Johnson Controls Unitary Products
12
(10)
208-3-60 16 110 25 15.6 110 24 2.3 13.5 1.1 8.6
None - - - 58 60 70 62 346 60.2 70 70 65 356
11725 12 1 33.3 63.9 70 70 62 346 66.6 70 70 65 356
12525 18.6 1 51.6 86.8 90 90 80 346 89.5 90 90 82 356
13225 24 1 66.6 105.5 110 110 97 346 108.3 110 110 100 356
14225 31.8 2 88.3 132.6 150 150 122 346 135.4 150 150 125 356
230-3-60 16 110 25 15.6 110 24 2.3 13.4 1 8.6
None - - - 57.9 60 70 62 346 59.9 60 70 64 341
11725 16 1 38.5 70.3 80 80 65 346 72.8 80 80 67 341
12525 24.8 1 59.7 96.8 100 100 89 346 99.3 100 100 91 341
13225 32 1 77 118.4 125 125 109 346 120.9 125 125 111 341
14225 42.4 2 102 149.6 150 150 138 346 152.1 175 175 140 341
460-3-60 7.8 52 12 7.8 52 12 1.3 6.7 0.5 8.6
None - - - 29.1 30 35 31 169 30.1 35 35 32 165
11746 16.5 1 19.8 35.8 40 40 33 169 37.1 40 33 34 165
12846 27.8 1 33.4 52.8 60 60 49 169 54.1 60 49 50 165
13346 33 1 39.7 60.7 70 70 56 169 61.9 70 56 57 165
14246 41.7 2 50.2 73.8 80 80 68 169 75.1 80 68 69 165
575-3-60 5.7 38.9 9 5.8 38.9 9 1.1 5.4 0.4 8.6 None - - - 22.3 25 25 24 129 23.1 25 25 25 126
14
(12.5)
208-3-60 19.6 136 31 19.6 136 31 5.8 13.5 1.1 8.6
None - - - 67.7 70 80 72 401 69.9 70 80 75 411
11725 12 1 33.3 67.7 70 80 72 401 69.9 70 80 75 411
12525 18.6 1 51.6 86.8 90 90 80 401 89.5 90 90 82 411
13225 24 1 66.6 105.5 110 110 97 401 108.3 110 110 100 411
14225 31.8 2 88.3 132.6 150 150 122 401 135.4 150 150 125 411
230-3-60 19.6 136 31 19.6 136 31 5.2 13.4 1 8.6
None - - - 67 70 80 71 397 69 70 80 74 402
11725 16 1 38.5 70.3 80 80 71 397 72.8 80 80 74 402
12525 24.8 1 59.7 96.8 100 100 89 397 99.3 100 100 91 402
13225 32 1 77 118.4 125 125 109 397 120.9 125 125 111 402
14225 42.4 2 102 149.6 150 150 138 397 152.1 175 175 140 402
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 6.7 0.5 8.6
None - - - 30.3 35 35 32 196 31.3 35 35 34 199
11746 16.5 1 19.8 35.8 40 40 33 196 37.1 40 33 34 199
12846 27.8 1 33.4 52.8 60 60 49 196 54.1 60 49 50 199
13346 33 1 39.7 60.7 70 70 56 196 61.9 70 56 57 199
14246 41.7 2 50.2 73.8 80 80 68 196 75.1 80 68 69 199
575-3-60 6.6 55.3 10 6.6 55.3 10 2.2 5.4 0.4 8.6 None - - - 24.2 25 30 26 164 25 25 30 27 165
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.
ZX04-14 Hi Static Indoor Blower - With Powered Convenience Outlet (Continued)
Size
(Tons)
Nominal
Unit
Voltage
Compressor 1 Compressor 2
OD
Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat
Field Installed Kit
2EK045*
MCA
1
(Amps)
Min
Fuse
2
/
Breaker
3
Size
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
Min
Discon-
nect
Rating
4
MCA
1
w/Pwr
Exh
(Amps)
Min
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Max
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Min
Discon-
nect
Rating
4
/
Pwr Exh
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA