User's Manual

1068152-YTG-L-0815
Johnson Controls Unitary Products 137
09
(8.5)
208-3-60 13.7 83.1 21 13.7 83.1 21 2.3 9.9 1.1
None - - - 45.3 50 50 48 258 47.5 50 60 51 268
11725 12 1 33.3 54 60 60 50 258 56.8 60 60 52 268
12525 18.6 1 51.6 76.9 80 80 71 258 79.6 80 80 73 268
13225 24 1 66.6 95.6 100 100 88 258 98.4 100 100 91 268
14225 31.8 2 88.3 122.8 125 125 113 258 125.5 150 150 115 268
230-3-60 13.7 83.1 21 13.7 83.1 21 2.3 9.4 1
None - - - 44.8 45 50 48 267 46.8 50 60 50 261
11725 16 1 38.5 59.9 60 60 55 267 62.4 70 70 57 261
12525 24.8 1 59.7 86.4 90 90 79 267 88.9 90 90 82 261
13225 32 1 77 108 110 110 99 267 110.5 125 125 102 261
14225 42.4 2 102 139.3 150 150 128 267 141.8 150 150 130 261
460-3-60 6.2 41 10 6.2 41 10 1.3 4.7 0.5
None - - - 21.3 25 25 23 134 22.3 25 25 24 130
11746 16.5 1 19.8 30.6 35 35 28 134 31.9 35 28 29 130
12846 27.8 1 33.4 47.6 50 50 44 134 48.9 50 44 45 130
13346 33 1 39.7 55.5 60 60 51 134 56.8 60 51 52 130
14246 41.7 2 50.2 68.6 70 70 63 134 69.9 70 63 64 130
575-3-60 4.8 33 8 4.8 33 8 1.1 4.3 0.4 None - - - 17.3 20 20 19 115 18.1 20 20 19 113
12
(10)
208-3-60 16 110 25 16 110 25 5.8 13.5 1.1
None - - - 55.3 60 70 59 345 57.5 60 70 62 355
11725 12 1 33.3 58.5 60 70 59 345 61.3 70 70 62 355
12525 18.6 1 51.6 81.4 90 90 75 345 84.1 90 90 77 355
13225 24 1 66.6 100.1 110 110 92 345 102.9 110 110 95 355
14225 31.8 2 88.3 127.3 150 150 117 345 130 150 150 120 355
230-3-60 16 110 25 16 110 25 5.2 13.4 1
None - - - 54.6 60 70 58 341 56.6 60 70 60 346
11725 16 1 38.5 64.9 70 70 60 341 67.4 70 70 62 346
12525 24.8 1 59.7 91.4 100 100 84 341 93.9 100 100 86 346
13225 32 1 77 113 125 125 104 341 115.5 125 125 106 346
14225 42.4 2 102 144.3 150 150 133 341 146.8 150 150 135 346
460-3-60 7.8 52 12 7.8 52 12 2.9 6.7 0.5
None - - - 27.2 30 30 29 166 28.2 30 30 30 168
11746 16.5 1 19.8 33.1 35 35 30 166 34.4 35 30 32 168
12846 27.8 1 33.4 50.1 60 60 46 166 51.4 60 46 47 168
13346 33 1 39.7 58 60 60 53 166 59.3 60 53 55 168
14246 41.7 2 50.2 71.1 80 80 65 166 72.4 80 65 67 168
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 5.4 0.4 None - - - 20.4 25 25 22 129 21.2 25 25 23 131
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.
ZYE04-12 High Static Indoor Blower - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Nominal
Unit
Voltage
Compressor 1 Compressor 2
OD
Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat
Field Installed Kit
2EK045*
MCA
1
(Amps)
Min
Fuse
2
/
Breaker
3
Size
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
Min
Discon-
nect
Rating
4
MCA
1
w/Pwr
Exh
(Amps)
Min
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Max
Fuse
2
/
Breaker
3
Size
w/
Pwr Exh
(Amps)
Min
Discon-
nect
Rating
4
/
Pwr Exh
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA