User's Manual

1068152-YTG-L-0815
170 Johnson Controls Unitary Products
ZX14 and ZY12
SAFETY AND KEY
CHARACTERISTICS PER
BE-PDP-STD-01
THIRD ANGLE PROJECTION
6.55
[166.4]
12.63
[320.7]
5.22
[132.6]
28.75
[730.3]
14.00
[355.6]
3.40
[86.3]
36.38
[923.9]
21.90
[556.1]
25.29
[642.3]
87.18
[2214.4]
61.69
[1566.9]
X
Y
7.29
[185.2]
33.94
[862]
9.48
[240.7]
4.23
[107.3]
2.33
[59.3]
40.17
[1020.3]
20.64
[524.1]
4.69
[119.1]
35.29
[896.4]
2.92
[74.1]
2.97
[75.5]
4.66
[118.3]
n 1.38
[34.9]
n 1.97
[50]
n 2.28
[57.9]
n 2.53
[64.3]
48.56
[1233.5]
6.70
[170.2]
28.38
[720.7]
8.19
[208]
4.93
[125.1]
36.38
[923.9]
5.00
[127]
5.00
[127]
13.88
[352.4]
12.63
[320.7]
38.05
[966.5]
6.19
[157.1]
DWJCRGG27375NEW DRAWING09-13-13A
ENGCKDREC NOREVISION RECORDDATE
REV
LEV
MATERIAL
TYPE
NOT APPLICABLE
ENG SPEC
NOT APPLICABLE
SIZE
DWG NO.
REV
UST-CDR-1ODFLT
B
PART NO.
SHT NO 1 OF 1
ALL PROPRIETARY RIGHTS IN THE SUBJECT MATTER HEREOF ARE RESERVED AND NO PERMISSION
IS GRANTED TO REPRODUCE THIS PRINT IN WHOLE OR IN PART OR DISCLOSE ANY OF THE
INFORMATION UPON IT TO OTHERS WITHOUT WRITTEN RELEASE BY JOHNSON CONTROLS
DRAWING PER ASME Y14.5M-1994
SUBMITTAL DWG, CDR,
1 ODF, 48.5" CAB
TOLERANCES UNLESS OTHERWISE SPECIFIED:
ONE PLACE DECIMAL = ` .1
TWO PLACE DECIMAL = ` .03
THREE PLACE DECIMAL = ` .010
ANGLES = ` 2~
DIMENSIONS ARE IN INCHES
DO NOT SCALE PRINT
JOHNSON CONTROLS
UNITARY PRODUCTS GROUP
NORMAN, OK 73069
NAME DATE
DRN
R.GUAJARDO 09-13-13
CHK
J.CARTER 09-13-13
ENG
D. WOODWARD09-13-13
MFG
SCALE
0.090
HAIL GUARD (OPTIONAL)
FRONT
VIEW
REAR
VIEW
RIGHT
VIEW
LEFT
VIEW
TOP
VIEW
DIRECTION OF AIRFLOW
CENTER OF GRAVITY
SUPPLY
RETURN
RETURN
BLOWER
ACCESS
DRAIN
FILTER ACCESS
ECONOMIZER HOOD
(OPTIONAL)
CONTROL/
COMPRESSOR
ACCESS
NOTES:
1. FOR OUTDOOR USE ONLY.
2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS.
3. RECOMMENDED MIN. CLEARANCES:
RIGHT SIDE: 18 [450] W/SIDE CONDENSATE DRAIN: 24 [600]
LEFT SIDE: 12 [300] W/PIGTAIL: 18 [450]
FRONT: 48 [1200]
BACK: 18 [450]
TOP: 72 [1800]
BOTTOM: 1 [25]
4. REMOVED.
5. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES
CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT.
6. DOWNFLOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY
ROOF CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, IT
IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED BY
CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS.
7. REMOVED.
8. MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES
THE LOWEST NEGATIVE STATIC.
9. DIMENSIONS IN [ ] ARE IN MILLIMETERS OR KILOGRAMS.
10. OPTIONAL COIL GUARDS, GAS HEAT, DISCONNECT SWITCH
SHOWN.
11. TOP PANEL EMBOSSMENTS NOT SHOWN FOR DIMENSION CLARITY.
12. HEAT EXCHANGER IS TYPICAL OF HIGH GAS HEAT OPTION.
SUPPLY
ALTERNATE
CONDENSATE DRAIN
POWER
ENTRY
CONVENIENCE
OUTLET
(OPTIONAL)
SEE DETAIL A
D
A
C
B
GAS INLET
EXHAUST FLUE
DETAIL A
SCALE 0.180
TONNAGE
U
N
I
T
OPERATING
WEIGHT (LBS)
(BASE UNIT)
CENTER OF GRAVITY
LOCATION (BASE UNIT)
4 POINT CORNER LOADS (LBS) (BASE UNIT)
XYABCD
12.5 ZX 941 [426.8] 45 [1125] 36 [900] 265 [120.2] 284 [128.8] 203 [92.1] 189 [85.7]
10 ZY 902 [409.1] 45 [1125] 36 [900] 249 [113.0] 267 [121.1] 199 [90.3] 186 [84.4]
B 12-03-14 REVISE CLEARANCES (NOTE 3), REMOVE EXTRA DIMS FROM VIEW A 37128 RGG TPS AJR
DISCONNECT SWITCH