User's Manual

1068152-YTG-L-0815
50 Johnson Controls Unitary Products
115°F 125°F
1250
77 60.0 6.0 30.3 24.3 18.2 - - - 54.5 6.7 28.8 22.8 16.8 - - -
72 56.3 5.9 39.5 32.5 25.6 18.6 - - 51.9 6.7 37.7 30.8 23.8 16.8 - -
67 52.7 5.9 48.7 40.8 32.9 26.0 19.1 - 49.4 6.6 46.7 38.7 30.8 24.0 17.2 -
62 51.0 5.8 50.1 45.2 40.3 33.4 26.5 19.6 48.5 6.5 47.3 42.5 37.7 31.1 24.5 17.8
1500
77 60.7 6.0 35.7 27.0 18.3 - - - 55.2 6.7 34.1 25.3 16.6 - - -
72 57.5 6.0 43.3 35.2 27.1 19.0 - - 53.0 6.6 41.2 33.2 25.1 17.1 - -
67 54.3 5.9 50.8 43.3 35.8 27.7 19.6 - 50.9 6.6 48.4 41.0 33.6 25.6 17.6 -
62 53.0 5.9 52.0 48.3 44.6 36.4 28.2 20.0 50.1 6.5 48.9 45.5 42.1 34.1 26.1 18.1
57 52.3 5.8 52.3 52.3 52.3 45.1 36.9 28.6 49.4 6.5 49.3 49.3 49.3 42.7 34.6 26.6
1750
77 61.3 6.0 41.1 29.8 18.4 - - - 56.0 6.7 39.3 27.8 16.4 - - -
72 58.6 6.0 47.0 37.8 28.6 19.4 - - 54.2 6.6 44.7 35.6 26.4 17.3 - -
67 56.0 5.9 52.9 45.8 38.7 29.4 20.0 - 52.3 6.6 50.1 43.3 36.5 27.2 17.9 -
62 54.9 5.9 53.8 51.4 48.9 39.4 29.9 20.4 51.7 6.6 50.5 48.5 46.6 37.2 27.7 18.3
57 54.4 5.9 54.4 54.4 54.4 49.4 39.8 30.1 51.1 6.6 50.8 50.8 50.8 47.1 37.5 28.0
2000
77 61.9 6.0 46.5 32.5 18.5 - - - 56.7 6.7 44.6 30.4 16.1 - - -
72 59.8 6.0 50.8 40.4 30.1 19.7 - - 55.3 6.6 48.2 38.0 27.8 17.5 - -
67 57.7 5.9 55.0 48.3 41.7 31.1 20.5 - 53.8 6.6 51.8 45.6 39.4 28.9 18.3 -
62 56.9 5.9 55.7 54.5 53.2 42.4 31.6 20.8 53.4 6.6 52.1 51.5 51.0 40.2 29.4 18.6
57 56.5 6.0 56.5 56.5 56.5 53.8 42.7 31.7 52.9 6.7 52.3 52.3 52.3 51.5 40.4 29.3
2250
72 60.9 6.0 54.5 43.1 31.6 20.1 - - 56.4 6.6 51.7 40.4 29.1 17.8 - -
67 59.3 5.9 57.1 50.8 44.6 32.8 21.0 - 55.3 6.6 53.5 47.9 42.3 30.5 18.7 -
62 58.9 6.0 57.6 57.6 57.5 45.4 33.3 21.2 55.0 6.7 53.7 53.7 53.7 43.2 31.0 18.8
57 58.6 6.0 58.2 58.2 58.2 58.1 45.6 33.2 54.6 6.7 53.8 53.8 53.8 53.8 43.3 30.7
2500
72 62.1 6.0 58.3 45.7 33.1 20.5 - - 57.5 6.6 55.2 42.8 30.4 18.0 - -
67 61.0 6.0 59.2 53.3 47.5 34.5 21.4 - 56.8 6.6 55.2 50.2 45.1 32.1 19.1 -
62 60.8 6.0 59.5 59.5 59.5 48.4 35.0 21.6 56.6 6.7 55.3 55.3 55.3 46.3 32.7 19.1
57 60.6 6.1 59.9 59.9 59.9 59.9 48.6 34.7 56.4 6.8 55.3 55.3 55.3 55.3 46.2 32.0
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZX06 (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65