115°F 125°F
1500
77 68.9 6.8 47.8 38.0 28.1 - - - 61.7 7.5 51.0 39.9 28.8 - - -
72 64.5 6.6 53.1 43.8 34.4 25.0 - - 59.1 7.4 53.3 43.5 33.7 24.0 - -
67 60.2 6.5 58.4 49.6 40.7 32.2 23.7 - 56.5 7.2 55.7 47.2 38.7 30.3 21.9 -
62 59.9 6.4 58.9 52.9 47.0 39.4 31.7 24.1 56.5 7.1 55.6 49.6 43.6 36.6 29.6 22.6
1800
77 70.4 6.7 45.4 34.0 22.7 - - - 63.8 7.5 44.0 32.4 20.8 - - -
72 66.6 6.6 53.0 43.2 33.4 23.7 - - 61.3 7.4 50.7 41.1 31.5 21.9 - -
67 62.8 6.5 60.6 52.4 44.2 34.1 23.9 - 58.8 7.3 57.4 49.8 42.1 32.0 22.0 -
62 62.4 6.5 61.1 58.1 55.0 44.4 33.9 23.3 58.6 7.2 57.5 55.1 52.7 42.2 31.7 21.2
57 62.0 6.5 61.7 61.7 61.7 54.8 43.9 33.0 58.5 7.2 57.5 57.5 57.5 52.4 41.5 30.5
2100
77 72.0 6.7 42.9 30.1 17.3 - - - 65.9 7.5 36.9 24.9 12.9 - - -
72 68.7 6.6 52.8 42.7 32.5 22.3 - - 63.5 7.4 48.0 38.6 29.2 19.8 - -
67 65.5 6.6 62.8 55.3 47.7 35.9 24.1 - 61.0 7.3 59.1 52.3 45.5 33.8 22.1 -
62 65.0 6.6 63.4 63.2 63.0 49.5 36.0 22.6 60.7 7.3 59.3 59.3 59.3 47.8 33.8 19.8
57 64.5 6.6 64.0 64.0 64.0 63.1 48.0 32.9 60.5 7.3 59.5 59.5 59.5 59.5 45.6 29.3
2400
77 73.6 6.7 40.4 26.1 11.9 - - - 68.0 7.4 29.9 17.4 4.9 - - -
72 70.9 6.6 52.7 42.1 31.6 21.0 - - 65.6 7.4 45.4 36.2 26.9 17.7 - -
67 68.1 6.6 65.0 58.1 51.3 37.8 24.3 - 63.3 7.4 60.9 54.9 48.9 35.5 22.2 -
62 67.5 6.6 65.7 65.7 65.7 54.6 38.2 21.8 62.8 7.4 61.2 61.2 61.2 53.4 35.9 18.4
57 66.9 6.6 66.4 66.4 66.4 66.4 52.1 32.8 62.4 7.4 61.4 61.4 61.4 61.4 49.7 28.0
2700
72 73.0 6.7 52.5 41.6 30.6 19.7 - - 67.8 7.4 42.8 33.7 24.6 15.6 - -
67 70.8 6.7 67.2 61.0 54.8 39.7 24.5 - 65.5 7.4 62.6 57.4 52.3 37.3 22.3 -
62 70.1 6.7 67.9 67.9 67.9 59.6 40.4 21.1 65.0 7.5 63.0 63.0 63.0 59.0 38.0 17.0
57 69.4 6.7 68.7 68.7 68.7 68.7 56.2 32.7 64.4 7.5 63.4 63.4 63.4 63.4 53.8 26.8
3000
72 75.1 6.7 52.4 41.0 29.7 18.4 - - 70.0 7.4 40.1 31.2 22.4 13.5 - -
67 73.5 6.7 69.4 63.8 58.3 41.5 24.8 - 67.8 7.5 64.3 60.0 55.7 39.0 22.4 -
62 72.6 6.8 70.2 70.2 70.2 64.7 42.5 20.3 67.1 7.6 64.8 64.8 64.8 64.6 40.1 15.6
57 71.8 6.8 71.0 71.0 71.0 71.0 60.3 32.6 66.3 7.7 65.4 65.4 65.4 65.4 57.9 25.6
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZX07 (6.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65