User's Manual

1068152-YTG-L-0815
56 Johnson Controls Unitary Products
115°F 125°F
2125
77 99.6 9.8 63.4 50.7 38.0 - - - 91.0 10.8 63.0 49.6 36.1 - - -
72 92.5 9.6 72.5 60.3 48.1 35.9 - - 84.9 10.6 70.4 58.1 45.7 33.4 - -
67 85.4 9.5 81.7 69.9 58.2 46.3 34.4 - 78.9 10.5 77.8 66.6 55.3 43.4 31.5 -
62 82.9 9.5 82.9 75.6 68.2 56.7 45.2 33.7 78.6 10.5 78.6 71.9 65.0 53.4 41.9 30.4
2550
77 102.7 9.8 67.4 51.5 35.6 - - - 95.9 10.8 66.3 49.6 33.0 - - -
72 95.6 9.7 76.1 62.6 49.2 35.7 - - 89.1 10.7 73.2 59.8 46.4 33.0 - -
67 88.5 9.6 84.7 73.7 62.7 49.0 35.3 - 82.2 10.6 80.2 70.0 59.8 46.0 32.3 -
62 86.5 9.6 85.9 81.1 76.3 62.3 48.3 34.4 82.0 10.6 81.1 77.2 73.2 59.1 45.0 30.8
57 86.3 9.5 86.3 86.3 86.3 75.6 61.4 47.2 81.8 10.6 81.8 81.8 81.8 72.1 57.7 43.2
2975
77 105.7 9.8 71.5 52.3 33.1 - - - 100.9 10.9 69.6 49.7 29.9 - - -
72 98.7 9.8 79.6 64.9 50.2 35.5 - - 93.3 10.8 76.1 61.6 47.1 32.6 - -
67 91.6 9.7 87.6 77.5 67.3 51.7 36.2 - 85.6 10.7 82.6 73.4 64.3 48.6 33.0 -
62 89.7 9.7 88.7 86.5 84.3 67.9 51.5 35.1 84.9 10.7 83.5 82.4 81.4 64.7 48.0 31.3
57 89.2 9.7 89.2 89.2 89.2 84.1 66.8 49.6 84.2 10.7 84.2 84.2 84.2 80.8 63.0 45.2
3400
77 108.8 9.9 75.5 53.1 30.7 - - - 105.9 10.9 72.8 49.8 26.8 - - -
72 101.8 9.8 83.1 67.2 51.3 35.4 - - 97.4 10.8 78.9 63.3 47.7 32.2 - -
67 94.7 9.8 90.6 81.2 71.8 54.4 37.1 - 89.0 10.8 84.9 76.8 68.7 51.3 33.8 -
62 93.0 9.8 91.5 91.5 91.5 73.5 54.7 35.8 87.8 10.8 85.8 85.8 85.8 70.4 51.1 31.7
57 92.2 9.8 92.2 92.2 92.2 92.2 72.3 52.0 86.7 10.8 86.6 86.6 86.6 86.6 68.3 47.1
3825
72 104.8 9.9 86.6 69.4 52.3 35.2 - - 101.6 10.9 81.7 65.1 48.4 31.7 - -
67 97.8 9.8 93.6 85.0 76.4 57.2 37.9 - 92.4 10.9 87.3 80.2 73.2 53.9 34.6 -
62 96.2 9.9 94.3 94.3 94.3 79.1 57.8 36.5 90.8 10.9 88.1 88.1 88.1 76.0 54.1 32.2
57 95.1 9.9 95.1 95.1 95.1 95.1 77.7 54.3 89.1 11.0 89.0 89.0 89.0 89.0 73.6 49.1
4250
72 107.9 9.9 90.1 71.7 53.4 35.0 - - 105.8 10.9 84.6 66.8 49.1 31.3 - -
67 100.9 9.9 96.5 88.7 80.9 59.9 38.8 - 95.8 11.0 89.7 83.7 77.6 56.5 35.4 -
62 99.5 10.0 97.2 97.2 97.2 84.7 61.0 37.3 93.7 11.0 90.5 90.5 90.5 81.6 57.2 32.7
57 98.1 10.0 97.8 97.8 97.8 97.8 83.2 56.7 91.6 11.1 91.3 91.3 91.3 91.3 78.9 51.1
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZX09 (8.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65