User's Manual

1068152-YTG-L-0815
62 Johnson Controls Unitary Products
115°F 125°F
750
77 36.2 3.6 20.4 16.1 11.7 - - - 32.5 4.2 20.0 15.3 10.7 - - -
72 34.0 3.5 23.8 19.7 15.6 11.5 - - 31.2 4.0 22.4 18.4 14.4 10.4 - -
67 31.7 3.5 27.1 23.3 19.4 15.3 11.2 - 29.9 3.9 24.9 21.5 18.2 14.2 10.1 -
62 30.3 3.5 29.0 26.2 23.3 19.2 15.1 10.9 28.6 3.9 27.3 24.6 22.0 17.9 13.8 9.7
900
77 36.5 3.6 23.3 17.6 11.9 - - - 32.7 4.1 22.7 16.6 10.5 - - -
72 34.6 3.5 26.1 21.3 16.6 11.8 - - 31.7 4.0 24.6 19.9 15.2 10.5 - -
67 32.8 3.5 29.0 25.1 21.2 16.4 11.6 - 30.7 3.9 26.6 23.3 19.9 15.1 10.3 -
62 31.6 3.5 30.5 28.2 25.9 21.1 16.2 11.4 29.6 3.9 28.5 26.6 24.6 19.8 14.9 10.0
57 30.7 3.4 30.7 30.7 30.6 25.7 20.8 16.0 28.5 3.9 28.5 28.5 28.5 24.4 19.4 14.5
1050
77 36.8 3.5 26.1 19.1 12.0 - - - 32.9 4.0 25.4 17.8 10.3 - - -
72 35.3 3.5 28.5 23.0 17.5 12.1 - - 32.1 4.0 26.8 21.4 16.0 10.5 - -
67 33.9 3.5 30.8 26.9 23.0 17.5 12.0 - 31.4 3.9 28.3 25.0 21.6 16.1 10.5 -
62 32.9 3.4 32.0 30.2 28.5 22.9 17.4 11.8 30.6 3.9 29.8 28.5 27.3 21.6 16.0 10.3
57 32.2 3.4 32.2 32.2 32.2 28.4 22.7 17.1 29.8 3.8 29.8 29.8 29.8 27.2 21.4 15.7
1200
77 37.1 3.5 29.0 20.6 12.2 - - - 33.0 3.9 28.0 19.1 10.1 - - -
72 36.0 3.5 30.8 24.7 18.5 12.4 - - 32.6 4.0 29.1 22.9 16.7 10.5 - -
67 35.0 3.4 32.7 28.7 24.8 18.6 12.4 - 32.1 3.8 30.1 26.7 23.3 17.0 10.7 -
62 34.2 3.4 33.5 32.3 31.1 24.8 18.5 12.2 31.5 3.8 31.0 30.5 29.9 23.5 17.1 10.6
57 33.7 3.4 33.7 33.7 33.7 31.0 24.7 18.3 31.0 3.8 31.0 31.0 31.0 30.0 23.4 16.8
1350
72 36.7 3.5 33.2 26.3 19.5 12.6 - - 33.0 4.0 31.3 24.4 17.5 10.6 - -
67 36.0 3.4 34.5 30.5 26.6 19.7 12.7 - 32.8 3.8 31.8 28.4 25.0 18.0 10.9 -
62 35.5 3.4 35.0 34.3 33.7 26.7 19.7 12.7 32.5 3.8 32.3 32.3 32.3 25.4 18.1 10.9
57 35.1 3.4 35.1 35.1 35.1 33.7 26.6 19.5 32.2 3.8 32.2 32.2 32.2 32.2 25.4 18.0
1500
72 37.4 3.5 35.5 28.0 20.5 12.9 - - 33.5 3.9 33.5 25.9 18.2 10.6 - -
67 37.1 3.4 36.4 32.4 28.4 20.7 13.1 - 33.5 3.8 33.5 30.1 26.7 18.9 11.1 -
62 36.7 3.4 36.5 36.4 36.3 28.6 20.8 13.1 33.5 3.8 33.5 33.5 33.5 27.2 19.2 11.2
57 36.6 3.4 36.6 36.6 36.6 36.4 28.5 20.7 33.5 3.8 33.5 33.5 33.5 33.5 27.4 19.1
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZY04 (3.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65