User's Manual

1068152-YTG-L-0815
64 Johnson Controls Unitary Products
115°F 125°F
1000
77 48.4 4.8 27.7 23.6 19.6 - - - 45.1 5.4 26.7 22.9 19.0 - - -
72 44.9 4.7 33.0 28.2 23.4 18.7 - - 41.0 5.3 31.6 27.0 22.4 17.7 - -
67 41.9 4.7 38.3 32.8 27.2 22.4 17.6 - 37.8 5.2 36.5 31.1 25.7 21.1 16.4 -
62 41.1 4.6 40.3 35.6 31.0 26.1 21.2 16.3 37.8 5.2 37.8 33.4 29.0 24.4 19.7 15.1
1200
77 48.6 4.8 31.7 25.3 18.9 - - - 45.1 5.4 30.6 24.3 18.1 - - -
72 46.1 4.7 36.1 30.2 24.3 18.4 - - 42.3 5.3 34.5 28.8 23.1 17.4 - -
67 43.6 4.7 40.5 35.1 29.7 23.7 17.7 - 39.5 5.3 38.4 33.3 28.1 22.3 16.5 -
62 42.9 4.7 42.2 38.7 35.1 29.0 22.9 16.7 39.5 5.2 39.5 36.3 33.1 27.2 21.3 15.4
57 42.2 4.6 42.2 42.2 40.6 34.3 28.0 21.8 39.5 5.2 39.5 39.3 38.1 32.1 26.1 20.1
1400
77 48.9 4.7 35.7 26.9 18.2 - - - 45.0 5.3 34.5 25.8 17.1 - - -
72 47.4 4.7 39.1 32.2 25.2 18.2 - - 43.6 5.3 37.5 30.6 23.8 17.0 - -
67 45.3 4.7 42.6 37.4 32.2 25.1 17.9 - 41.3 5.3 40.4 35.5 30.5 23.5 16.5 -
62 44.7 4.7 44.1 41.7 39.3 31.9 24.5 17.1 41.3 5.2 41.2 39.2 37.2 30.0 22.8 15.7
57 44.1 4.6 44.1 44.1 44.1 38.7 31.1 23.6 41.3 5.2 41.3 41.3 41.3 36.5 29.2 21.8
1600
77 49.1 4.7 39.7 28.6 17.4 - - - 44.9 5.3 38.4 27.3 16.2 - - -
72 48.7 4.7 42.2 34.2 26.1 18.0 - - 44.9 5.3 40.4 32.5 24.6 16.6 - -
67 47.0 4.7 44.8 39.8 34.7 26.4 18.1 - 43.1 5.3 42.4 37.7 32.9 24.7 16.6 -
62 46.5 4.7 46.0 44.7 43.4 34.8 26.2 17.5 43.1 5.2 43.0 42.1 41.3 32.9 24.4 16.0
57 46.1 4.6 46.1 46.1 46.1 43.2 34.3 25.4 43.0 5.2 43.0 43.0 43.0 41.0 32.2 23.5
1800
72 49.9 4.7 45.3 36.1 27.0 17.8 - - 46.3 5.3 43.3 34.3 25.3 16.3 - -
67 48.7 4.7 46.9 42.1 37.2 27.7 18.2 - 44.9 5.3 44.4 39.9 35.3 26.0 16.6 -
62 48.3 4.7 47.9 47.7 47.5 37.7 27.8 17.9 44.8 5.3 44.7 44.7 44.7 35.7 26.0 16.2
57 48.0 4.6 48.0 48.0 48.0 47.6 37.4 27.2 44.8 5.2 44.8 44.8 44.8 44.8 35.3 25.2
2000
72 51.2 4.7 48.4 38.1 27.9 17.6 - - 47.6 5.3 46.2 36.1 26.0 15.9 - -
67 50.4 4.8 49.1 44.4 39.8 29.1 18.4 - 46.7 5.4 46.4 42.1 37.8 27.2 16.7 -
62 50.1 4.7 49.8 49.8 49.8 40.5 29.4 18.3 46.6 5.3 46.5 46.5 46.5 38.5 27.5 16.5
57 49.9 4.6 49.9 49.9 49.9 49.9 40.5 29.0 46.5 5.2 46.5 46.5 46.5 46.5 38.4 26.9
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZY05 (4.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65