Manual
Page 27
26800-90(K)
INPUTWINDSPEED(FREQ) WindspeedsignalinputonFREQ
 chan=01 channel01.ResultstoredinDLOC
 sensor=051xx 001
 units=M/S
 dloc=001
INPUTWINDDIR(VOLTAGE) Winddirectionsignalinputon
 chan=01 VIN1.ResultstoredinDLOC002.
 sensor=051xx
 dloc=002
INPUTVOLTAGE 0-1VTemperaturesignalmeasured
 chan=05 ondifferentialVINpair5/6ata
 type=DIFF rateof60Hz.MULTandOFFS
 mult=0.10000 scalesignalto-50to+50C.Result 
 offs=-50.000 storedinDLOC003.
 rate=60Hz
 dloc=003
INPUTVOLTAGE 0-1VRHsignalmeasuredondiffer-
 chan=07 entialVINpair7/8atarateof60Hz.
 type=DIFF MULTandOFFSscalesignalto0
 mult=0.10000 to100%RH.ResultstoredinDLOC
 offs=0.00000 004.
 rate=60Hz
 dloc=004
DISPLAYVALUE WindspeedinSLOC001displayed
 sloc=001 onscreen1usingbigfontatrow/
 scrn=1 column1/02.WIDTHandDECPT
 font=BIG dene00.0format.
 row=1
 col=02
 width=4
 decpt=1
DISPLAYVALUE WinddirectioninSLOC002dis-
 sloc=002 playedonscreen1usingbigfont
 scrn=1 atrow/column1/07.WIDTHand
 font=BIG DECPTdene000format.
 row=1
 col=07
 width=3
 decpt=0
DISPLAYVALUE TemperatureinSLOC003display-
 sloc=003 edonscreen1usingbigfontat
 scrn=1 row/column1/11.WIDTHand
 font=BIG DECPTdene000.0format.
 row=1
 col=11
 width=5
 decpt=1
DISPLAYVALUE RHinSLOC004displayedon
 sloc=004 screen1usingbigfontatrow/
 scrn=1 column1/17.WIDTHandDECPT
 font=BIG dene000format.
 row=1
 col=17
 width=3
 decpt=0
IFTIMEINTERVAL Flag1issetwhenthetopoftheminute
 unit=MIN (00secondsintotheminute)isreached.
 time=0001 We'llusethisagtoalignourstatistical
FLAGSET calculationsanddatarecordingwith
 ag#=01 uniformtimeintervals.
 state=ON
ENDIF ENDIFforIFTIMEINTERVAL
AVERAGE TheAVERAGEandMAXIMUMinstructions
 sloc=001 processvaluesfromtheirrepectiveSLOCs.
 dloc=011 BecauseweuseBLOCKtype,theresulting
 type=BLOCK calculatationsarecontrolledbyFLAG1
 #samp=00000 ratherthan#SAMP.Notethatwind
AVERAGE directionaverageusestheBLKANGLE
 sloc=002 type.
 dloc=012
 type=BLKANGLE
 #samp=00000
AVERAGE
 sloc=003
 dloc=013
 type=BLOCK
 #samp=00000
AVERAGE
 sloc=004
 dloc=014
 type=BLOCK
 #samp=00000
MAXIMUM
 sloc=001
 dloc1=021
 type=BLOCK
 #samp=00000
IFFLAG Whentimealignswiththetopofthe
 ag#=01 minute,recordtheaveragewindspeed,
 state=ON winddirection,temperature,RHand
RECORDTIME maximumwindspeed.
 frmt=DATE
RECORDTIME
 frmt=TIME
RECORDVALUE
 sloc=011
RECORDVALUE
 sloc=012
RECORDVALUE
 sloc=013
RECORDVALUE
 sloc=014
RECORDVALUE
 sloc=022
ENDIF ENDIFforIFFLAG
FLAGSET TurnFLAG1OFFsostatisticalinstructions
 ag#=01 canbegincollectingnewsamples.
 state=OFF
PGMEND
EXAMPLE USER PROGRAM
This program takes wind speed and direction measure-
ments from a Young 05103 Wind Monitor and Temperature/
RH measurements from a Young 41382V Temp/RH Sensor.
The execution interval is set to 1 iteration per second. 
Instantaneous measurements are displayed on screen 1. 
Averages for all values and maximum wind speed are calcu-
lated and recorded once per minute.