PROFIBUS connection System 182 XT-4
7 - 2
ba76027e01 02/2012
Have admissible bus parameters been set only? If you are in doubt
set them to default values.
Is it guaranteed that the PROFIBUS master has consistent access
to the 16 byte sensor data structure?
Note for Siemens PLC with programming language STEP7:
The following commands have to be used for consistent access:
SFC15 (for writing)
SFC14 (for reading)
After commissioning:
Do all devices signal error-free behavior?
(DIQ/S 182 XT-4-PR: status "Online" in the measured value and
status display).