Datasheet

NP7-6
Nominal voltage 6 V
20-hr rate Capacity to 1.75VPC at 20°C 7 Ah
10-hr rate Capacity to 1.75VPC at 20°C 6.5 Ah
Length 151 (±1) mm
Width 34 (±1) mm
Height mm
(height over terminals) 97.5 (±2) mm
Mass (typical) 1.32 kg
FASTON (Quickfit / release) 4.75 mm
Storage
Charge
Discharge LAYOUT
Capacity loss per month at 20°C (approx) 3 %
Standard Option
Flame retardant option (FR)
6.825 (±1%) V
2.275 (±1%) V/cell
Float Charge voltage temperature correction factor
(for variations from the standard 20°C)
-3 mV/cell/°C
7.25 (±3%) V
2.42 (±3%) V/cell
Cyclic Charge voltage temperature correction factor
(for variations from the standard 20°C)
-4 mV/cell/°C
Float charge current limit No limit A
Cyclic (or Boost) charge current limit 1.75 A
1 second 210 A
1 minute 48 A
Internal resistance N/A mΩ 3RD PARTY CERTIFICATIONS
Short-Circuit current N/A A ISO 9001 - Quality Management Systems
ISO 14001 - Environmental Management Systems
Measured at 1 kHz 28 mΩ EN 18001 - OHSAS Management Systems
UNDERWRITERS LABORATORIES Inc.
Refer to the technical manual NP
STANDARDS
EUROBAT Classification: Standard Commercial
3 to 5 years IEC61056
Yuasa design life @ 20°C
up to 5 years
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
Issue No.: V.2 / Issue Date: Mar 2011
VRLA Batteries release hydrogen gas which can form explosive mixtures in air. Do not place inside a sealed
container
Recycling
YUASA's VRLA batteries must be recycled at the end of life in accordance with local and national laws and
regulations
Batteries must not be suspended by their handles (where fitted)
Vent valves
Each cell is fitted with a low pressure release valve to allow gasses to escape and then reseal.
Gas Release
Installation
Can be installed and operated in any orientation except permanently inverted
Handles
SHORT-CIRCUIT CURRENT & INTERNAL RESISTANCE
(according to EN IEC 60896-21)
IMPEDANCE
DESIGN LIFE
PERFORMANCE & CHARACTERISTICS
CHARGE VOLTAGE
-20°C to +60°C
-15°C to +50°C
SAFETY
Float charge voltage at 20°C
Cyclic (or Boost) charge at 20°C
CHARGE CURRENT
MAXIMUM DISCHARGE CURRENT
NP-Series - Valve Regulated Lead Acid Battery
-20°C to +60°C
ABS (UL.94:HB)
ABS (UL94:V0)
SPECIFICATIONS
DIMENSIONS
TERMINAL TYPE
OPERATING TEMPERATURE RANGE
STORAGE
CASE MATERIAL

Summary of content (1 pages)