OWNER'S MANUAL • Assembly • Installation • Operation • Repair Parts • Maintenance Tips NH O K YU U GLE A E / SKY I Model No. LWO-112 (Oil Fired) LWG-112 (Gas Fired) LWO-168 (Oil Fired) LWG-168 (Gas Fired) CAUTION: Read Rules And Instructions Carefully For Safe Operation YUKO N POLA R /EAGL E II Oil/Wood - Gas/Wood Warm Air Central Heating Furnaces IMPORTANT: Installation must be made in accordance with NFPA, and state and local ordinances which may differ from this installation manual.
FOR YOUR SAFETY: If you smell gas: 1. Open windows 2. Do not touch electrical switches 3. Extinguish any open flame 4. Immediately call your gas supplier FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. DANGER RISK OF FIRE OR EXPLOSION Do not burn garbage, gasoline, drain oil, kerosene, thinners, etc. WARNING RISK OF FIRE Tightly close the firing door and ash door during operation.
TABLE OF CONTENTS INTRODUCTION Safety Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2, 4 Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Statements STOP FOR SAFETY! Safe assembly, operating and maintenance practices should always be followed whenever using any equipment. Wherever you see the caution sign, extra safety precautions should be taken. You must stop, read, and carefully follow the safety instructions before proceeding. READ THROUGH THE ENTIRE MANUAL It is recommended to read through the entire manual before beginning your installation and/or operating your furnace. Follow all steps exactly.
Unpack and Check Your Cartons INSPECT SHIPMENT Your furnace is shipped complete in three cartons. Note any damage to the shipping cartons. Remove all items from your shipping cartons. Check all items against the packing list below. Note any items lost or damaged in shipment. Refer to the exploded view and parts list in the back of the manual for the part names and numbers of missing or damaged items. Keep the small parts in the parts bag until you are ready to install them. PACKING LIST 1.
Furnace Features - Eagle I - Husky burner side. This firebrick not only protects the steel from the extreme combustion temperatures in the firebox, but it also retains a substantial amount of heat after the wood/coal fire burns down. YUKONTROL SOLID-STATE FURNACE CONTROL This is the solid-state control that coordinates the gas or oil burner function with the wood/coal damper so that your home is always comfortable using your choice of fuels.
Furnace Features - Eagle I - Husky 7
Furnace Features - Eagle II - Polar YUKONTROL SOLID-STATE FURNACE CONTROL This is the solid-state AFTER-BURNERTM JET SYSTEM GIVES MAXIMUM SOLID FUEL BURNING EFFICIENCY It extracts maximum BTUs from control that coordinates the gas or oil burner function with the wood/coal damper so that your home is always comfortable using your choice of fuels. the wood or coal. Superheated air is introduced above the fire to ignite and extract heat from the unburned combustible gases.
Furnace Features - Eagle II - Polar 9
Specifications MODEL LWO-112 (Oil) Input rating ......................................................................................................................................140,000 BTU/HR Nozzle ..............................................................................................................................................1.0 G.P.H. - 80 H Burner ........................................................................................................................................
Plan Your Installation Unit Dimensions PLAN YOUR INSTALLATION LWO-112 & LWG-112 It is recommended to read through the entire manual before beginning your installation. Follow all steps exactly. Reading this manual will also help you get all the benefits from your furnace. CAUTION: Read these rules and the instructions carefully. Failure to follow these rules and instructions could cause a malfunction of the furnace. This could result in death, serious bodily injury and/or property damage.
Plan Your Installation CLEARANCES TO COMBUSTIBLES ABOVE TOP OF WARM AIR PLENUM FROM THE FRONT 6” FROM SIDES AND BACK 48” FROM CHIMNEY CONNECTOR 18” * 18” 6 FT OF PLENUM BEYOND 6 FT OF PLENUM 6” 1” Floor Joist or Combustible Material 1” Heat Supply Ducts 6 Inches ! CAUTION ! BE SURE TO INSTALL DUCT WORK WITH CLEARANCES SHOWN WARM AIR PLENUM FURNACE Combustible Walls Top View Cold Air Plenum 18” MIN 1” CLEARANCE TO COMBUSTIBLES BEYOND 6’ TO A POINT WHERE THERE IS A CHANGE IN DIRECTION OF 9
Plan Your Installation TYPICAL INSTALLATION DUCTS AND PLENUMS SHALL BE CONSTRUCTED ENTIRELY OF SHEET METAL. FIG. 5 AIR CONDITIONING COIL MUST BE INSTALLED WITH A METAL CONDENSATE PAN. DO NOT USE PLASTIC PAN DUCTS SHOULD BE LARGE ENOUGH TO HANDLE GRAVITY AIR FLOW IN THE EVENT OF ELECTRIC POWER OR FURNACE FAN FAILURE.
Installation PLACE FURNACE Review all instructions in the Planning Your Installation section. Place the furnace in the preselected location. Refer to Figs. 4 & 5 (on page 12) in the Planning Your Installation section. Make sure the furnace is level. RETURN AIR PLENUM WARM AIR PLENUM FUME SWITCH (GAS MODEL ONLY) SECONDARY AIR INTAKE COVER 1. Remove secondary air intake cover from accessory package and align over mounting holes located above fire door assembly on face of furnace. See Fig. 7. 2.
Installation CUT AWAY VIEW BURNER COMBUSTION CHAMBER OIL BURNER INSTALLATION • Model LWO-112 burner has a (140,000 BTU input) 1.00 G.P.H. 80 degree H nozzle installed at the factory. • Model LWO-168 burner has a (189,000 BTU input) 1.35 G.P.H. 80 degree H nozzle installed at the factory. Install burner as follows: 1. Make sure hole in side of pyrolite chamber lines up with hole in the end of the blast tube. (See Fig. 9) 2. Remove nuts from burner mounting studs on face of the furnace. 3.
Installation DRAW COLLAR (Models LWO-168 & LWG-168 ONLY) Firmly attach the draw collar around the stainless steel smoke pipe. Keep the field installed smoke pipe at least 2 " away from draw collar. This will insure that smoke leaving the furnace will not be drawn into the circulating air stream. See Fig. 11. SMOKE PIPE NOTE: Only Models LWO-168 and LWG-168 are equipped with a draw collar.
Installation SMOKE BAFFLES The smoke baffles are factory installed. They must be checked to see that they have not become dislodged during shipping. See Fig. 14-A. Complete the following steps to check the baffles: 1. Hold the baffle in proper position. Tilt the rear up to clear baffle mounting brackets. 2. Push baffle up to top of combustion chamber above all three brackets, level off, slide left and lower onto mounting brackets. 3. Check to see that all three brackets are engaged. 4.
Installation INSTALLING THE HONEYWELL FAN/LIMIT CONTROL Included in the accessory carton is a white sheet metal bracket that is 8-1/4 inches high and 3-1/4 inches wide. It has a 7/8” hole in it 6 inches from the bottom. Right below the 7/8” hole are 2 screw holes. This bracket also has 2 screw mounting holes on the bottom 1-1/4 inch flange. (Shown in Fig. 15) 1. Place the sheet metal plenum on top of the 24” X 24” warm air duct opening. 2.
Installation MOUNTING THE THERMOSTATS The thermostats must be mounted on an interior centrally located wall. Place them away from direct sunlight, drafts, and approximately 5 feet above the floor. It is not required that they be level. Place them right next to each other. See Fig. 17. Two Honeywell digital thermostats are furnished with all multi-fuel furnaces. The larger thermostat controls your gas, oil or electric, whichever back-up fuel you have.
Installation FUEL TANKS AND FUEL LINES Fuel tanks and fuel lines must be installed in accordance with requirements of NFPA 31. If fuel lines are under 30 feet in length, it is satisfactory to use 3/8" O.D. copper tube. Never use tube smaller than 3/8" O.D. If the lines are over 30 feet in length, we recommend 1/2" O.D. tube. Use good flare connections on the fuel lines and, whenever possible, avoid splicing the tube. Never make a splice or joint underground.
Installation GAS PIPE SIZING Check with your local gas supplier to determine total gas load for all your gas appliances. Size pipe accordingly. GAS PIPING All piping must comply with local codes. In the absence of local codes, follow the national fuel gas code ANSIZ233.1. A sediment trap or drip leg must be installed in the supply line to burner. (See Fig. 19) A union must be installed in the gas line. It should be adjacent to and upstream from the control manifold.
Installation FUME SENSOR (GAS MODELS ONLY) The FUME SENSOR is a manual reset heat/pressure sensor. It will shut down the gas burner. This occurs when there is a chimney down draft, plugged chimney, plugged smoke pipe, or a plugged secondary heat exchanger. If the gas burner shuts down because of any of the above conditions, before the burner can restart, you must press the red button down to manually reset it. Wire per schematic shown in Exploded View section in back of manual.
Installation ELECTRIC WIRING All electrical wiring must be done in accordance with the National Electrical Code. The code needs to be legally authorized in the area where the installation is being made. The circuit protector device must be located in a convenient place near the furnace. No lighter than 14 AWG wire should be used in the furnace power supply circuit.
Volt Field Wiring OIL OR GAS AND WOOD HEATING ONLY Honeywell FocusPro 5000 Thermostat Honeywell FocusPro 6000 Thermostat RC R Y C W RC R G Y C W G 24 volt Transformer R C C Terminal 1 controls wood damper/wood thermostat R 1 2 T Terminal 2 controls gas/oil burner thermostat T OIL or GAS BURNER T T OIL OR GAS AND WOOD HEATING WITH AIR CONDITIONING Honeywell FocusPro 6000 Thermostat Fan Relay RC R Y C W G Honeywell FocusPro 5000 Thermostat RC R Y C W G 24 volt Transformer
Installation CAUTION: Do not use any smoke pipes less than 24 gauge between furnace and chimney. CONNECTING SMOKE PIPE Set the smoke pipe end of the furnace as close to the chimney as possible. The rise of the smoke pipe toward the chimney must be at least one inch per linear foot of pipe. Do not exceed 10 feet in length. A clean out tee should be installed for removal of soot and fly ash. Do not install smoke pipe longer than necessary to reach chimney. This is for purposes of trapping heat.
Installation DO NOT ATTACH DRAFT CONTROL TO TOP OR BOTTOM OF FLUE PIPE, NOR IN ROOM SEPARATED FROM APPLIANCE. BEST LOCATION IS AS CLOSE TO APPLIANCE AS POSSIBLE. IMPORTANT A MANOMETER MUST BE USED TO ACCURATELY ADJUST FLUE DRAFT IMPORTANT: MAKE THESE ADJUSTMENTS WHEN INSTALLING. VERTICAL FLUE: Adjustment weight must be in RIGHT HAND SLOT (Marked “V”) in bracket on gate. The arrow on flap at bottom of gate must line up with letter “V” on lower right part of gate.
Installation PROPER CHIMNEYS The National Fire Protection Association (NFPA) requires that all factory built chimneys be Listed and installed in accordance with conditions of the Listing in the manufacturers instructions. NFPA also requires that your chimney extend at least three (3) feet above the highest point when it passes through the roof and at least two (2) feet higher than any portion of the building within ten (10) feet of the chimney.
Installation Questions? Visit www.yukon-eagle.
Installation COMBUSTION AIR Make-up outside air must be provided to furnace for proper fuel combustion. This is provided by openings to outside of building. These openings shall have unobstructed areas not less than the areas of the flue pipe. See Figs. 25, 26, 27 IMPORTANT: Outside air is needed to replace air used by the burner and wood combustion process. Outside air is required to replace air used for taking the by-products of combustion out the chimney.
Installation FURNACE LOCATED IN CONFINED SPACE When the furnace is in utility room, install two open grilles. (See Fig. 28.) Place them in a wall or door opening to the rest of the house. One grille will supply combustion air. Locate it near the floor. The other grille is for ventilation. Locate it close to the ceiling. Each grille must have a free area. It should be not less than one square inch for each 1000 BTU/hr. of the total input rating of appliances in confined space.
Operating Instructions OIL FIRING THE UNIT To start the oil burner on a new installation 1. Check to make sure there is oil in the storage tank. No. 2 fuel oil may be used if tank is in the basement or buried below ground. No. 1 fuel oil is recommended if the tank is outside and above ground. 2. The oil burner was started and tested at the factory. Double check to make sure the proper oil burner nozzle is installed and electrodes are set according to the oil burner manual. 3.
Operating Instructions Gas Firing the Unit To Start the Gas burner on new installation 1. With gas line in “off” position, install burner using gasket and tighten down with 3 nuts to furnace. 2. Connect 110 Volt power to burner 3. Connect 24 Volt power to the burner from the DS-103 Versatrol. 4. Set room thermostat 10 degrees above room temperature. 5. Allow burner to operate for 2 minutes until all air is purged from gas line. 6.
Operating Instructions BEST WOOD TO BURN All solid fuel, whether it is coal, pine, oak or any grain has about 12,000 BTU's per pound if its moisture content is zero. Wood that has been cut, split and air dried for 2 years has about 8,000 usable BTU's per pound. Hardwood such as oak or hard maple has nearly twice the BTU's per cord as pine or aspen because it is nearly twice as heavy. Freshly cut wood has about 50% moisture content. Wood that has been cut and split for 2 years has about 20%.
Operating Instructions STARTING WOOD FIRE WITH GAS OR OIL BURNER Place three or four 6 to 8 inch diameter logs in the firebox. Set the temperature on the small thermostat to the desired setting. Set the temperature on the larger thermostat above room temperature. The flame from the burner need not touch the wood to ignite. HAND FIRING WOOD Set the small thermostat above room temperature. Set the larger thermostat below room temperature. The damper to the firebox should now be open.
Operating Instructions WHAT SIZE COAL SHOULD I BURN? The air space between the furnace grates is 1/2 inch. Therefore, coal smaller than 1/2 inch can fall through the grates into the ash pan. • Pea size coal ranges from 9/16 to 11/16 inch. • Nut size coal ranges from 1-3/16 to 1-5/8 inches. • Stove size coal ranges from 1-5/8 to 2-7/16 inches. Nut size is preferred by most people and is recommended for use in this furnace. Anthracite coal is hard and burns like charcoal that is used in your barbecue grill.
Operating Instructions OPERATING INSTRUCTIONS FOR BURNING COAL ON 1/2-INCH OPENING GRATES (Optional) The following instructions are for burning various types of coal, storage of coal, and the cleaning of the furnace. Some coal is oil-treated at the mine. Some users have indicated that it tends to make the coal difficult to start. Burning coal requires some patience and a regular procedure. With improper tending, a coal fire can go out in a short time.
Wiring Diagrams OIL AND WOOD HEATING ONLY Questions? Visit www.yukon-eagle.
Wiring Diagrams OIL AND WOOD HEATING WITH A/C 38
Wiring Diagrams GAS AND WOOD HEATING ONLY 39
Wiring Diagrams GAS AND WOOD HEATING WITH A/C 40
Maintenance GRATE CARE - ASH REMOVAL It is necessary that ashes be removed from the ash pan on a daily basis. The ashes should never be allowed to accumulate high enough to come in contact with the grates. Such a condition could cut off necessary air circulation. It could also result in a warping or burnout of grates. ASH DISPOSAL Unlike wood ashes, coal ash should not be spread on the garden. The minerals in coal ash contains several chemicals which could be harmful to plant life.
Maintenance SMOKE PIPE, CHIMNEY AND SECONDARY HEAT EXCHANGER Do not burn green or freshly felled wood. This may cause creosote and soot to build up in chimney, smoke pipe, and secondary heat exchanger. These should be checked and cleaned several times each heating season. CLEANING FURNACE AND CHIMNEY FLUE PIPES Frequently check and clean the furnace flue pipes and chimney. Soot and fly ash should not be allowed to build up on any of these surfaces. Chimneys are best cleaned professionally.
Maintenance FURNACE BLOWER ADJUSTMENT Set adjustable motor pulley so blower will give approximately 80-90º F temperature rise through furnace. After pulley has been adjusted check bolt as follows: The belt is drawn tight during shipment. Therefore both belt tension and sheave alignment must be rechecked by the installer. This is done when the furnace is placed in service. FIG. 36 Improper belt tension and pulley misalignment are the major causes of furnace fan noise.
Maintenance DUCT WORK AND BLOWER SPEED ADJUSTMENT Supply and return duct system should be sized properly for efficient operation. Normal air temperature rise through the furnace should be adjusted to approximately 80-90º F. Proper blower speed adjustment, in conjunction with adequate duct work are necessary to achieve this. A high temperature rise will result in excessive fuel usage. This is due to the high stack temperature that always accompanies a high air temperature rise.
Maintenance TESTING INSTALLATIONS FOR EFFICIENCY A Draft gauge must be used. Draft in smoke pipe must be set at -.03 Water Column updraft. Failure to set properly will cause fuel to be wasted, heating will not be satisfactory, fast buildup of creosote in heat exchanger and chimney may occur and cause damage to your heating system.
Maintenance TEST PROCEDURE Step 1. Set the thermostat high enough so that the unit will run for at least 15 minutes, the maximum time that should be required for the test. Let the unit operate enough for the stack temperature to stabilize. Step 2. For your initial set of readings, set the Draft Regulator so that there is -.03 Water Column Draft in the smoke pipe between the flue outlet and draft regulator. A manometer must be used to properly set the draft to -.03” WC. Step 3.
Maintenance FIREBRICK PLACEMENT Models (LWO-112 & LWG-112 ONLY) (Fig. 42) Model LWO-112 & LWG-112 (Left Hand Model Shown) Lower Row 1. Place 3 ea. 12”x 6” bricks at rear of firebox 2. Place 4 ea. 12”x 6” bricks on side opposite burner. 3. Place 4 ea. 9” x 6” bricks on burner side. Upper Row 1. Place 2 ea. 9” x 6” bricks at rear of firebox. The 9- inch side lying down. 2. Place 1 ea. 9” x 6” and 1 ea. 12”x6” bricks on side opposite burner. The 9-inch and 12-inch side lying down. 3.
Maintenance OIL BURNER MAINTENANCE MAINTENANCE AT THE END OF THE HEATING SEASON: 1. Shut off electric current to burner at fuse panel. 2. If oil filter has not been cleaned recently, it should be removed and cleaned. (Consult instruction card furnished with fuel unit). 3. Oil storage tank should be kept filled to prevent water vapor from collecting. It is suggested the valve in the suction line be closed. Oil storage tank should be cleaned every 2 or 3 years.
Maintenance Maintenance HOW TO PREVENT RUST AND CORROSION At the end of each heating season, clean both primary and secondary heat exchangers. Also, clean the ash pan thoroughly. Paint the inside of the heat exchanger with automobile crankcase oil. This will decrease rusting caused by summer moisture. The black paint on firing door area may wear or burn off. It can be repainted with a high temperature, flat black, air-drying paint. CLEANING THE CHIMNEY, SMOKE PIPE AND HEAT EXCHANGER Avoid chimney fires.
Maintenance TOP OF CHIMNEY LOWER THAN SURROUNDING OBJECTS REMEDY: EXTEND CHIMNEY ABOVE ALL OBJECTS WITHIN 30 FEET. SMOKE IN THE FURNACE ROOM This condition is usually caused because smoke is not being drawn up through the chimney. Other causes could be a failed (firebox)heat exchanger. Check with your qualified furnace service provider. CHIMNEY CAP PUSHED OVER FLUE OR FLU OBSTRUCTED BY A VENTILATOR REMEDY: REMOVE OBSTRUCTION Chimney causes: ACCUMULATION OF SOOT OR DEBRIS IN OFFSET REMEDY: REMOVE 1.
Maintenance OVER HEATING WHEN BURNING SOLID FUEL AS YOUR PRIMARY SOURCE OF HEAT If your home is overheating, your furnace is providing heat when the thermostat is satisfied. One of these ideas will help with overheating. 1. The best answer is to use fewer logs at each filling. This provides the maximum amount of heat while conserving wood. 2. There are 3 pegs in the fan and limit control. One peg is set at 250º F. Never change this setting. The middle peg is set at 150º F.
Exploded Views & Parts List EAGLE I - HUSKY MODELS LWO-112 & LWG-112 52
Exploded Views & Parts List REPAIR PARTS-Combustion Chamber Assembly (Left Hand Shown) EAGLE I- HUSKY OIL/GAS-SOLID FUEL COMBINATION FURNACE Models LWO-112 and LWG-112 Key No.
Exploded Views & Parts List EAGLE II - POLAR MODELS LWO-168 & LWG-168 54
Exploded Views & Parts List (Left Hand Shown) EAGLE II - POLAR OIL/ GAS-SOLID FUEL COMBINATION FURNACE Models LWO-168 and LWG-168 Key No.
Exploded Views & Parts List WAYNE MODEL MSR OIL BURNER GUN ASSEMBLY Questions? Visit www.yukon-eagle.
Exploded Views & Parts List BURNER COMPONENTS WAYNE MODEL MSR PA R T D E S C R I P T I O N A N D PA R T N U M B E R W H E N O R D E R I N G PA R T S NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 1 2 3 4 5 6 Part Description Motor, 1/7 HP 120/60/3450 1.7A PSC Blower Wheel 3.12” WX 4.25” OD Burner Housing Motor Cord Cover J-Box Transformer Housing Cover Slot Cover Plate Inner Air Band Outer Air Band Coupling Oil Line Assembly Fuel Unit Elbow Gun Assembly Air Tube 8.
Exploded Views & Parts List WAYNE MODEL P250AF-DIN GAS BURNER 58
Exploded Views & Parts List BURNER COMPONENTS WAYNE MODEL P250AF-DIN PART DESCRIPTION AND PART NUMBER WHEN ORDERING PARTS Key No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 * * 16 17 18 19 20 21 22 23 24 25 26 27 28 29 * Part Description Control Box Cover ASM Time Delay Relay Transformer 24V/30VA Control Box/Strap ASM Bracket Ignition Module H-S8751008 DI Ignition Wire ASM Tube Electrode ASM Pilot Shield Gasket Adjustable Flange (Incl.
Exploded Views & Parts List CIRCULATING FAN PERFORMANCE CURVE CHART MODELS LWO-112 AND LWG-112 THIS CIRCULATING FAN PERFORMANCE CURVE CHART IS FOR DETERMINING MOTOR HORSEPOWER NEEDS 60
Exploded Views & Parts List CIRCULATING FAN PERFORMANCE CURVE CHART MODELS LWO-168 AND LWG-168 THIS CIRCULATING FAN PERFORMANCE CURVE CHART IS FOR DETERMINING MOTOR HORSEPOWER NEEDS 61
Troubleshooting SERVICE HINTS- OIL Problem: If your furnace is not heating or giving enough heat. Cause: Thermostat is not set correctly Correction: Check to see that thermostat is set on "HEAT" position and heat anticipator is set properly. Reset thermostat above room temperature. Cause: Burner is not firing properly Correction: Contact your local service man Cause: No power to furnace Correction: Check fuse or circuit breaker. If fuse is blown, replace. IF breaker is tripped, reset.
Notes Model Number: __________________________________ Serial Number:__________ Installation Date:_______________________Contractor_________________________ Service Calls:__________________________________________________________________ _______________________________________________________________________ _______________________________________________________________________ _________________________________________________________________ ________________________________________________________________
YUKON EAGLE YUKON-EAGLE I - HUSKY YUKON-EAGLE II - POLAR OIL/WOOD - GAS/WOOD OWNER'S MANUAL • Assembly • Installation • Operation • Repair Parts For Model’s LWO-112 (Oil Fired) LWG-112 (Gas Fired) LWO-168 (Oil Fired) LWG-168 (Gas Fired) WARM AIR CENTRAL HEATING FURNACES HOW TO ORDER REPAIR PARTS WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE FOLLOWING INFORMATION: • PART NUMBER • PART DESCRIPTION • MODEL NUMBER ALL PARTS MAY BE PURCHASED FROM A YUKON DEALER OR DIRECT FROM OUR FACTORY.