Install Instructions

Page 6 of 18
DOUBLE WALL:
1. Align pipes and push them together until the snap-lock
engages. (Illustration #1A, Images 4, 5 & 6).
Proper pipe orientation is essential to achieve effective
condensate flow. In most cases the use of an appliance
specific flue collar adaptor is required to connect directly to
the appliance. This adaptor will configure the vent orientation
with the gasket end of pipe and fittings towards termination.
Also:
Some flue collars may require the use of high temperature
silicone sealant to make a positive pressure gas tight seal. In some cases a clamping mechanism may be necessary to
secure the adaptor to the appliance.
IMAGES BELOW SHOW DOUBLE WALL PIPE CONNECTION
Image 4 Image 5
Image 6
SYSTEM SYSTEM OPERATING
TEMPERATURE
CLEARANCE
ENCLOSED VERTICAL
CLEARANCE
UNENCLOSED
HORIZONTAL VERTICAL
SINGLE WALL
550°F (288°C)
480 F (249 C)
300 F (149 C)
6” (150 mm)
4” (100 MM)
4” (100 MM)
Pipe 3” (76 mm)
Thimble-6”(25 mm)
1” (25 MM)
1” (25 MM)
3” (152 mm)
1” (25 MM)
1” (25 MM)
DOUBLE WALL
550°F (288°C)
480 F (249 C)
300 F (149 C)
6” (150 mm)
4” (100 MM)
4” (100 MM)
Pipe-2” (51 mm)
Thimble-3” (76 MM)
1” (25 MM)
1” (25 MM)
2” (51 mm)
1” (25 MM)
1” (25 MM)
Table 2
NOTICE
Illustration 1A