FEATURES
TECHNICAL PARAMETERSDESCRIPTION
APPEARANCE
ASM-01
Input (supply) terminals: L, N
Input rated voltage: 230 V~
Input voltage tolerance: from -15 to +10%
Nominal frequency: 50 / 60 Hz
Rated power consumption: 48 mA
Supply/release terminals: IN / IN (connected inside the device)
Power/relay supply indicator: red LED
Time adjustment range: from 10 sec to 10 min
Time accuracy adjustment: ±10 %
Time repeatability adjustment: ±5 %
Time adjustment: fluent rotational potentiometer
Output relay parameters: 1NO - 16A/250 V AC1 4000 VA
Number of terminal clamps: 4
Section of connecting cables: from 0,2 to 2,50 mm
2
Ambient temperature range: from -20 to +45
o
C
Operating position: free
Mounting: TH35 rail (PN-EN 60715)
Protection degree: IP20 (PN-EN 60529)
Protective class: II
Overvoltage category: II
Pollution degree: 2
Rated impulse withstand voltage: 1 kV (PN-EN 61000-4-5)
Dimensions (height / width / depth): monomodular(17,5mm) 90x17,5x66mm
Weight: 0,073 kg
Reference standards: PN-EN 60669-1; PN-EN 60669-2-1
PN-EN 61000-4-2,3,4,5,6,11
● Staircase lighting control,
● operating time adjustment from 10
sec to 10 min,
● power supply indicator – red LED
diode,
● cooperation with monostable
pushbuttons equipped with illumina-
tion lamps,
● cooperation with 3-wire or 4-wire
installation,
● voltage relay output max 16 A
capacity,
● monomodular casing.
The staircase lighting time delay
switch ASM-01 is used to control ligh-
ting devices on staircases and corridors.
After releasing the system it switches
on the lighting for the preset time by the
user. After that it switches off automa-
tically. The operating time can be adju-
sted from 10 s to 10 min by means of the
potentiometer placed on the front panel
of the device. The staircase lighting time
delay switch ASM-01 can be used as
standard time delay relay.
The device is designed
for one-phase installation
and must be installed in
accordance with stan-
dards valid in a particular
country. The device sho-
uld be connected accor-
ding to the details included in this opera-
ting manual. Installation, connection and
control should be carried out by a quali-
fied electrician staff, who act in accordan-
ce with the service manual and the device
functions. Disassembling of the device is
equal with a loss of guarantee and can
cause electric shock. Before installation
make sure the connection cables are not
under voltage. The cruciform head screw-
driver 3,5 mm should be used to instal the
device. Improper transport, storage, and
use of the device influence its wrong func-
tioning. It is not advisable to instal the de-
vice in the following cases: if any device
part is missing or the device is damaged
or deformed. In case of improper functio-
ning of the device contact the producer.
CAUTION
Time adjustment
Power/relay supply
Input (supply) terminal (L) Input (supply) terminal (N)
indicator
Supply/release terminals
(IN, IN)
The symbol stands for selective
collection of electrical and
electronic devices. Placing used
devices with other waste is not
allowed