Operation Manual

ZENNiOAVANCEYTECNOLOGÍA www.zennio.com
29
THERMOSTAT Æ Select the type of control to carry out:
Only Heat
Only Cool
Heat & Cool
REFERENCE TEMPERATURE Æ
 For every enabled
thermostat in the Z38, users will be asked by parameter whether to
use the internal sensor measure as a reference, or if on the other
hand an external sensor will be used. The same parameterization
field offers also the possibility to choose a proportion between both
measures (Z38 internal sensor + external sensor).
Proportion Z38 Internal Sensor External Sensor
1 75% 25%
2 50% 50%
3 25% 75%
The resulting measure is exclusively used by the thermostat in the
Z38, and cannot be shown through any available Communication
object.
FREEZING PROTECTION Æ Regardless of the status the
thermostat may be (On/Off), when “Freezing Protection” is
activated, the system will be warned to automatically keep the
temperature always above a value (Protection Temperature) selected
by parameter.
¾ Protection Temperature
: This parameter fixes the minimum
temperature the user will accept.
9 Protection Temperature is measured in ºCelsius.
9 There is no connection between the “Set Temperature”
and the “Protection Temperature”.
9 This is the real temperature to be applied as freezing
protection.
9 Thermostat will turn Off when temperature in the room
reaches “Protection Temperature + 1ºC”
OVERHEATING PROTECTION Æ Regardless of the status the
thermostat may be (On/Off), when “Overheating Protection” is
activated, the system will be warned to automatically keep the
temperature always below a value (Protection Temperature) selected
by parameter.