Freezing protection: Allows acting over the thermostat automatically if the
temperature measured reaches a minimum temperature value defined in the
"Protection Temperature" parameter (ºC). The system is able to react instantaneously
to face this situation, maintaining the temperature always above this fixed value. This
protection only has effect with the thermostat switched off.
Control method: choose the way the thermostat will control the temperature:
2 point control with hysteresis (it requires configuring the lower and upper
hysteresis).
Proportional integral control (PI): continuous or PWM (it requires
configuring the cycle time and its control parameters).
Additional heating: enabling this field, the auxiliary system is asked to
contribute to reach the “Set temperature” as soon as possible. The additional heating
band (in tenths of degree) must be configured.
Thermostat Function: Cooling. Configure the following features:
Overheating protection: Allows acting over the thermostat automatically if the
temperature measured reaches a maximum temperature value defined in the