"Protection Temperature" parameter (ºC). The system is able to react instantaneously
to face this situation, maintaining the temperature always below this fixed value. This
protection only has effect with the thermostat switched off.
Control method: the same as for "Heating".·
Additional cooling: enabling this field, the auxiliary system is asked to
contribute to reach the “Set temperature” as soon as possible. The additional cooling
band (in tenths of degree) must be configured.
Thermostat Function: Heating and Cooling. When the two modes are selected, a
new drop-down box appears "Heating/Cooling automatic switching", to configure whether
the the transition between modes is carried out automatically (Always enabled), manually
(Always disabled) or making use of 1 bit communication object ("1" to enable and "0" to
disable). Moreover, the Heating an Cooling screens are shown.
Enable special modes (Comfort, Night, Standby): the modes Comfort, Night and
Standby are enabled, and the clima reaction can be chosen, among:
It remains OFF and nothing changes
It remains OFF but Setpoint temperature is updated
Setpoint temperature changes and clima turn ON
Startup setting: to configure the status of the thermostat after a bus power failure
(Last, ON, OFF).
Reference temperature: to select the source of the reference temperature: Source
1, Source 2 or a proportion between both measures (Proportion 1: 25%-75%; Proportion
2: 50%-50%; Proportion 3: 75%-25%).
Sending statuses on bus voltage recovery: A new box will appear to parameterize
the delay (in seconds) after which the thermostat statuses will be sent to the KNX bus.
Note: For further information about the thermostat of Zennio products working, please refer to the
document Clima I - Zennio Thermostat available in the documentation area in the site:
http://www.zennio.com.