Operation Manual

ZENNiO AVANCE Y TECNOLOGÍA
23
The available options are:
Rising edge: select the sending value when this edge happens:
Nothing (no action is performed).
0: the object "[Ix][Sensor] Edge" is sent to the KNX bus with value "0".
1: the object "[Ix][Sensor] Edge" is sent to the KNX bus with value "1".
Switching: sending "0" or "1" to the KNX bus, as appropriate.
Falling edge: select the sending value when this edge happens: Nothing, 0, 1 or
switching.
Sending of "0" Delay: specify the time, in seconds, after which the value "0" will be sent,
once received the corresponding order.
Sending of "1" Delay: specify the time, in seconds, after which the value "1" will be sent,
once received the corresponding order.
Periodical sending of "0": define a cyclical sending, in seconds, of the value "0". The
value 0 indicates that the periodical sending is not activated.
Periodical sending of "1": define a cyclical sending, in seconds, of the value "1". The
value 0 indicates that the periodical sending is not activated.
Block: if "Yes" is chosen, a new 1-bit communication object "[Ix] Block" is enabled, to
block or unblock the corresponding input (sending a "1" or a "0", respectively). Meanwhile the
input is blocked, any order received from the KNX bus will be ignored (excepting the alarm,
which has priority over the rest of functionalities).
Sending statuses on bus voltage recovery: this option allows configuring an automatic
sending of the input status after a voltage recovery, with a sending delay (value between 2
and 255, in seconds).