3.3.2. TEMPERATURE PROBE
When configuring an input as a temperature probe, the following options can be configured:
Figure 3.16. Input: Temperature probe
Temperature sensor calibration: to re-calibrate (setting the tenths of degree) the sensor
to take as reference any other sensor present in the installation, thus synchronizing the
measurement of the two.
Temperature sending period: to select by parameter the time (in tens of second) to
send cyclically to the KNX bus the current temperature measurement. The value 0 indicates
that the periodical sending is not activated.
Send with a temperature change: the current temperature will be only sent to the KNX
bus when it has changed (increased or decreased) with regard to the last measure, the
amount of degrees specified in this parameter (from 0 to 200 tenths of degree).
Temperature protection: to select an overheating, overcooling or both protection.
Depending on the chosen protection, one or two communication objects will be enabled: "[Ix]
Overheating" and "[Ix] Overcooling", which will indicate (with the value "1") if the
corresponding temperature has been exceeded. It is necessary to define the overheating or
the overcooling temperature (or both), in tenths of degree, as well as an hysteresis value.