Dimming step
Necessary pulsations for a complete
regulation (0-100%)
(1). 100% 1
(2). 50% 2
(3). 25% 4
(4). 12.5% 8
(5). 6.25% 16
(6). 3.1% 32
(7). 1.5% 64
Table 3.1. Dimming step
Shutter: it allows controlling the movement of shutters by means of two binary objects:
"[Bxy] Move shutter" ("0"=Up and "1"=Down) and "[Bxy] Stop shutter" and 1-byte object "[Bxy]
Shutter position", which indicates the position of the shutter, in percentage, at any time
(100%=Down, 0%=Up).
Decrease button: a long press moves down the shutter while a short press stops the
shutter, sending the value "1" through the object "[Bxy] Stop shutter".
Increase button: a long press moves up the shutter while a short press stops the
shutter, sending the value "0" through the object "[Bxy] Stop shutter".
Scaling: allows sending a percentage by means of the object "[Bxy] Scaling" associated
to the couple of buttons.
Decrease button: a short press decreases the percentage value one by one while a
long press decreases the value 10 by 10.
Increase button: a short press increases the percentage value one by one while a
long press increases the value 10 by 10.
Counter: allows sending an integer value by means of the object "[Bxy] Counter"
associated to the couple of buttons.
Decrease button: a short press decreases the counter value one by one while a long
press decreases the value 10 by 10.
Increase button: a short press increases the counter value one by one while a long
press increases the value 10 by 10.