Operation Manual

ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com
32
SECTION
NUMBER
SIZE
IN/OUT
FLAGS
VALUES
NAME
DESCRIPTION
RANGE
1st TIME
RESET
BUTTONS
31-34 4 bits O
TR
0-15 0 Last
[Bxy] Light Dimming
4-bits dimmer control
35-38 1 byte O
TR
0-255; 0-100% 0 Last
[Bxy] Light indicator
0%=Off; 100%=On
[Bxy] Shutter position
0%=Top; 100%=Bottom
[Bxy] Scaling
1 byte generic control
[Bxy] Counter
1 byte generic control
[Bxy] Enumeration
1 byte generic control
39-42 2 bytes I/O
TRW
0-100ºC 25ºC Last
[Bxy] Temperature control
from 0ºC to 100ºC
43-46 1 bit O
TR
0/1 Indifferent Indifferent
[Bxy] Stop Shutter
0 or 1 -> Stop
47 2 bytes I/O
TRW
0-100ºC 25ºC Last
[Arrows] Temperature control
from 0ºC to 100ºC
48-55 1 bit I/O
TRW
0/1 0 Last
[Bx] Binary control
1-bit generic control
[Bx] Binary control: press
1-bit generic control
56-63 1 bit O
TR
0/1 0 Last
[Bx] Binary control: release
1-bit generic control
101-108 1 byte O
TR
0-255 Indifferent Last
[Bx] 1 byte value
0-255
109-116 2 bytes O
TR
0-65535
0-120.0
Indifferent Last
[Bx] 2-byte value (unsigned int)
0-65535
[Bx] 2-byte value (float)
0-120.0
INPUTS
64-65 1 bit I
W
0/1 0 Last
[Ix] Block
1=Input disabled; 0=Input free
66-67 1 bit O
TR
0/1 0 0
[Ix] [Sensor] Edge
Edge -> Sending of "0" or "1"
70-71 2 bytes O
TR
0-95ºC 25ºC Last
[Ix] Current temperature
Temperature sensor value
72-73 1 bit O
TR
0/1 0 Last
[Ix] Overcooling
1=Overcooling; 0=No Overcooling
74-75 1 bit O
TR
0/1 0 Last
[Ix] Overheating
1=Overheating; 0=No Overheating
PRESENCE
SIMULATION
68 1 bit I
W
0/1 0 Last
Presence simulation
0=Disabled; 1=Enabled