SECTION
NUMBER
SIZE
IN/OUT
FLAGS
VALUES
NAME
DESCRIPTION
RANGE
1st TIME
RESET
PRESENCE
SIMULATION
69 1 bit O
TR
0/1 0 Last
Simulation channel
0=Off; 1=On
MENU
THERMOSTAT
76 1 bit I
TW
0/1 0 Indifferent
Thermostat - ON/OFF
0=Off; 1=On
77 1 bit O
TR
0/1 0 Last
Thermostat - ON/OFF Status
0=Off; 1=On
78 2 bytes I
TW
0-95ºC 25ºC Last
Setpoint Temperature
from 0ºC to 95ºC
79 2 bytes O
TR
0-95ºC 25ºC Last
Setpoint status
from 0ºC to 95ºC
80 1 bit I
TW
0/1 0 Last
Cool/Heat
0=Cool; 1=Heat
81 1 bit O
T
0/1 Indifferent Indifferent
Control variable (Cool)
2 point control
Control variable (Cool)
Proportional integral (PWM)
82 1 bit O
T
0/1 Indifferent Indifferent
Control variable (Heat)
2 point control
Control variable (Heat)
Proportional integral (PWM)
83 1 byte O
T
0-255 Indifferent Indifferent
Control variable (Cool)
Proportional integral (Continuous)
84 1 byte O
T
0-255 Indifferent Indifferent
Control variable (Heat)
Proportional integral (Continuous)
85 1 bit O
T
0/1 0 0
Additional cool
Temp > (Setpoint+Band) => "1"
86 1 bit O
T
0/1 0 0
Additional Heat
Temp < (Setpoint+Band) => "1"
87 1 bit I
TW
0/1 0 Last
Comfort mode
1=Set comfort mode; 0=No action
88 1 bit I
TW
0/1 0 Last
Noght mode
1=Set standby mode; 0=No action
89 1 bit I
TW
0/1 0 Last
Standby mode
1=Set comfort mode; 0=No action
90 2 bytes I
W
0-95ºC 26ºC Last
Comfort setpoint (cool)
Temperature for comfort mode