Operation Manual

ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com
34
SECTION
NUMBER
SIZE
IN/OUT
FLAGS
VALUES
NAME
DESCRIPTION
RANGE
1st TIME
RESET
MENU
THERMOSTAT
91 2 bytes I
W
0-95ºC 23ºC Last
Comfort setpoint (heat)
Temperature for comfort mode
92 2 bytes I
W
0-95ºC 28ºC Last
Night setpoint (cool)
Temperature for night mode
93 2 bytes I
W
0-95ºC 21ºC Last
Night setpoint (heat)
Temperature for night mode
94 2 bytes I
W
0-95ºC 30ºC Last
Standby setpoint (cool)
Temperature for standby mode
95 2 bytes I
W
0-95ºC 19ºC Last
Standby setpoint (heat)
Temperature for standby mode
96 2 bytes I
W
0-95ºC 25ºC Last
Temperature source 1
External sensor value temp.
97 2 bytes I
W
0-95ºC 25ºC Last
Temperature source 2
External sensor value temp.
98 1 bit I
W
0/1 0 Last
Heating/Cooling automatic switching
1=Enabled; 0=Disabled
REMOTE
CONTROLLER
99 1 bit O
T
0/1 0 Last
[IR] F1
1-bit generic control
100 1 bit O
T
0/1 0 Last
[IR] F2
1-bit generic control