Installation guide
Installation – Mounting Height & Clearance
6
www.zephyronline.com
DUCTING
A minimum of 6” round or 3-1/4” x 10” rectangular 
duct work must be used to maintain maximum air 
fl ow effi ciency with the 600 cfm internal blower. 
A minimum of 10” to 8” round duct work must be 
used with the 1000 cfm external blower.
Always use rigid type metal ducts only. Flexible 
ducts could restrict air fl ow by up to 50%.
Use calculation (on page 5) to compute total 
available duct run when using elbows, transitions 
and caps.
ALWAYS, when possible, reduce the number or 
transitions and turns. If long duct run is required, 
increase duct size from 6” to 7 or 8”. If a reducer is 
used, install a long reducer instead of a pancake 
reducer. Reduce duct size as far away from 
opening as possible.
If turns or transitions are required; install as far 
away from opening and as far apart, between 2, 
as possible.
Minimum mount height between range top and 
hood bottom should be no less than 24”. 
Maximum mount height should be no higher than 
32”.
It is important to install the hood at the proper 
mounting height. Hoods mounted too low could 
result in heat damage and fi re hazard; while hoods 
mounted too high will be hard to reach and will 
lose its performance and effi ciency.
If available, also refer to range manufacturer’s 
height clearance requirements and recommended 
hood mounting height above range.
Vertical Ducting:
6” round minimum (internal blower)
10” to 8” round minimum (external blower)
Horizontal Ducting:
3-1/4”x10” minimum (internal blower)
No horizontal option available for external blower
DAMAGE-SHIPMENT / INSTALLATION:
•  Please fully inspect unit for damage before 
installation.
•  If the unit is damaged in shipment, return the 
unit to the store in which it was bought for 
repair or replacement.
•  If the unit is damaged by the customer, repair 
or replacement is the responsibility of the 
customer.
•  If the unit is damaged by the installer (if other 
than the customer), repair of replacement must 
be made by arrangement between customer 
and installer.
36”
24” min.
32” max.