User manual
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT-201-7-2 PAGE 9
Issue: 1.2 Authorised: Date: 27/3/2012
7. DISABLEMENTS
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM.
Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For
example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is
possible for the user to disable that zone during the risk period and then enable it again afterwards. During a disablement
of a zone(s), no fire or fault signal will be processed for that zone(s). Only zone(s) in a non-alarm state can be disabled,
that is zones already in fire cannot be disabled.
External sounders can also be disabled as could be required in certain conditions.
7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS.
1. Enter the access code (default 1245) and press
2. Hold the Disable button for 3 seconds
3. Type the number of the zone you want to disable. If you want to disable a sounder press “Start Sounders”
button
4. Press to disable the selected zone or sounder.
5. To exit the disable mode, Hold the Disable button for 3 seconds
Showing all the Disabled Zones.
1. Enter access code and press
2. Press Disable
7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS.
1. Enter access code and press
2. Press and hold Disable button for 3 seconds Disable and zone light flash
3. Press
4. Press and hold the disable button for 3 seconds Disable LED goes out
5. Press three times to exit
NOTES:
The option of disabling or enabling zones 2, 3, 4, 5, 6, 7 and 8 is only available if these zones are present on the
panel