22
means not enabled.
Table 3-5 Parameters on the alarm interface
Parameter
Description
Anti-passback
After the anti-passback is enabled, users need to verify identities both for
entry and exit; otherwise an alarm will be triggered.
If a person enters with the identity checked and exits without the
identity checked, an alarm will be triggered when the person tries to
enter again and the person will have no permission to unlock the door
any more.
If a person enters without the identity checked, an alarm will be triggered
when the person tries to exit with the identity checked, and the person
will have no permission to unlock the door any more.
Duress
After enabling the duress function, an alarm will be triggered when a
duress card or duress password is used to unlock the door.
Illegal Card
Exceeding
Time
After an unauthorized card is used to unlock the door more than 5 times in
50 seconds, an alarm will be triggered.
3.8.4 Door Status
There are three options: NO, NC, and Normal.
NO: If NO is selected, the door stays open, which means the door will never be closed.
NC: If NC is selected, the door stays closed, which means the door will not be unlocked.
Normal: If Normal is selected, the door will be unlocked and locked depending on your
settings.
3.8.5 Lock Holding Time
Lock Holding Time is the duration in which the lock is unlocked. If the lock has been unlocked
for a period that exceeds the duration, the lock will be automatically locked.
Network Communication 3.9
To make the terminal work normally, you need to configure parameters for network, serial ports
and Wiegand ports.
3.9.1 IP Address
3.9.1.1 IP Configuration
Configure an IP address for the terminal to make it be connected to the network.