User's Manual
30 FD1043V User Manual
of the door sensor is inconsistent with that of the door sensor mode, the alarm will be triggered. This time period is
the
Door Sensor Delay (valid value: 1 to 99 seconds).
[Door Sensor Type]: There are three option: No, Normally Open, and Normally Closed.
No means door sensor is not in use;
Normally Open means the door is always opened in power-on condition;
Normally Closed means the door is always closed in power-on condition.
[Door Alarm Delay (s)]: When the state of the door sensor is inconsistent with that of the door sensor type, alarm will
be triggered after a time period; this time period is the
Door Alarm Delay (valid value: 1 to 99 seconds).
[Alarm]: Select the turn on the alarm function.
12.2 Wiegand Output Setting
Click on [Wiegand output setting] to set the related parameters, as shown below:
Field Instruction:
[Type]: Displays default User ID and it cannot be modified.
[Wiegand output bits]: The default is Wiegand34. Other options are Wiegand26, Wiegand26a, and Wiegand34a.
[Pulse Width (us)]: The default value is 100, the range is 20-400.
[Pulse Interval (us)]: The default is 1000, the range is 200-20000.
[Failed ID]: It is defined as the output value for failed user verification. The output format depends on the [Wiegand
Format] setting. It’s disabled by default; the range is 0 - 65535.
[Site Code]: Used to customize the Wiegand format. It is almost similar to device ID, the only difference is that, it can